Model AV2-N4X

AV2-N4X Instruction Manual

Rev. 1.1

Page 5 of 6

4.0 Troubleshooting



Tools Required:
Digital volt-ohm meter
Refer to

Figure 2 Wiring Diagram

.


Verify proper voltage is being applied to the strobes and siren by measuring with the digital voltmeter
probes (see specifications label located inside the enclosure to determine correct voltage).

Strobe: measure voltage from the second terminal on the terminal strip to the third terminal.

Siren: measure voltage from the second terminal on the terminal strip to the fourth terminal.

If power is being provided and the corresponding strobe or siren does not activate, return the alarm
station for repair or replacement as discussed in section 6.0 (

Warranty

) of this manual or replace damaged

components as referred to in section 5(

Spare Parts List

)

5.0 Spare Parts List


Part #

Description

3019-1

7 pin Terminal Block

027-002627-000 Strobe

Gasket

027-24412-0

Siren

Gasket


Strobe Light

354-49506-

Color of strobe Voltage

2 – Red

124 – 12 to 80 VDC

4 – Amber

120 – 120 VAC

5 – Green

240 – 240 VAC

6

Blue

7

Magenta

9

Clear


Siren

356-000-

Voltage

Type

Voltage

350 – VAC

012 – 12 VDC

450 – VDC

024 – 24 VDC

120

120VAC

240

240VAC