7. If applicable, connect alarm devices. Discreet alarm relay contacts are provided for three alarms: Fault,
Low and High. The contacts consist of common and choice of normally open or normally closed. Contact
output selections are jumper programmable on the sensor connector board. See the sensor manual for con-
tact ratings and other information.
8. If applicable, connect flow fault alarm wiring. Two sets of form C contacts (common, normally open and
normally closed) are provided. Relay contacts are rated 1 amp at 30VDC/.24 amp at 125VDC.
9. If applicable, connect RS-485 wiring.

The RS-485 requires 24 gauge, two conductor, shielded, twisted pair

cable between sensor and host PC. Use Belden part number 9841. Two sets of terminals are located on the
connector board to facilitate serial loop wiring from sensor to sensor. Wiring designators are +, –, and shield.

1.2 START UP

Upon completion of all tubing connections and field wiring turn on the power switch located on the enclo-
sure door. Note that the power lamp illuminates. If applicable, note that the sensor LCD indicator activates.
Varying readings may occur during sensor warm-up. Allow approximately 1 hour to stabilize (24 hours is best).

Also note air flow through the flow meter. Adjust the flow meter as necessary so that it falls between 500
and 1000 ml/m (milli liters per minute).

Assure that all field tubing connections are secure by obstructing the end of the sample line and observ-

ing that the flow meter decreases to “0” flow.

1.3 FLOW FAULT/LIQUID LEVEL DETECTION

Flow fault and liquid level detection consists of a circuit board assembly located on the motherboard.
Features of the circuit include a door mounted flow fault/liquid level indicator lamp.

Detcon Model 971-071170-LRY Gas Detection System PG.4

COM

NO

NC

Flow Fault

Liquid Level

Detection

Circuit

PT1

User Available
Dry Contacts

Flow fault adjust potentiometer

Fault indicator LED

P7

P8

mA

C NO/NC C NO/NC C NO/NC

SENSOR #1

FAULT

ALARM CONTACTS #1

ALARM 1 ALARM 2

ALARM DRY

CONTACTS

COM

NO/NC

COM

COM

NO/NC

NO/NC

FLT ALM 1 ALM 2

mA

4-20mA

Wire alarms and the 4-20mA output
signal to the plug-type connectors.

P10

P11

mA

C NO/NC C NO/NC C NO/NC

SENSOR #2

FAULT

ALARM CONTACTS #2

ALARM 1 ALARM 2

ALARM DRY

CONTACTS

COM

NO/NC

COM

COM

NO/NC

NO/NC

FLT ALM 1 ALM 2

mA

4-20mA

P6

P5

L1 L2 GND

117 VAC

IN

24 VDC

IN

Battery

Backup

Wire 117 VAC & optional 24 VDC
backup to the lugless connectors.

P9

Shld

SENSOR #1

RS-485

RS-485

P12

Shld

SENSOR #2

RS-485

RS-485