Model FP-524D

FP-524D Instruction Manual

Rev. 1.4

Page 36 of 39

1000 ohms maximum loop load @ 24VDC
0mA

All Fault Diagnostics

2mA

In-Calibration

4-20mA

0-100% full-scale

22mA

Over-range condition

Status Indicators:

4-digit LED Display with gas concentration, full-script menu
Prompts for AutoSpan, AutoZero, Set-up Options, and Fault Reporting

Faults Monitored:

Loop Fault, Input Voltage Fault, Zero Fault, Sensor Fault,
Processor Fault, Memory Fault, Calibration Fault(s)

Cable Requirements:

Power/Analog: 3-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG

Mechanical Specifications

Length:

8 inches (200mm), including Splashguard

Width:

5.5 inches (140mm)

Weight:

2.7lbs (3.4Kg)

Mechanical Connection:

¾” Male NPT threaded connection

Electrical Connection:

three 14 gauge (maximum) wire terminal landings