Model FP-524D
FP-524D Instruction Manual
Rev. 1.4
Page 32 of 39
Faulty 4-20mA Output
If sensor has a normal reading with no faults displayed, and the 4-20 mA signal output is 0mA….
Check that wiring is properly connected at terminal blocks and through to controller inputs.
The 4-20mA output loop must be closed (resistance of < 1000 ohms) to avoid the Loop Fault.
Perform a “Signal Output Check” sequence via Section 3.5.6 and verify 4-20mA output with current meter.
Swap with a known-good transmitter module to determine if the transmitter module’s 4-20mA output circuit is
faulty.
If the 4-20mA current loop is still out of tolerance, contact Detcon at
, or contact Detcon
customer service.
See also other documents in the category Detcon Sensors:
- TP-700 (48 pages)
- TP-700 SIL 2 Safety Manual (6 pages)
- FP-700 (50 pages)
- FP-700 SIL 2 Safety Manual (6 pages)
- IR-700 (50 pages)
- IR-700 SIL 2 Safety Manual (6 pages)
- DM-700 (58 pages)
- DM-700 SIL 2 Safety Manual (6 pages)
- PI-700 (64 pages)
- PI-700 0-500ppb (59 pages)
- DM-634 (21 pages)
- PI-600 (37 pages)
- DM-600IS (41 pages)
- IR-640 (24 pages)
- IR-622 (24 pages)
- FP-624D-HT (48 pages)
- FP-524HT (22 pages)
- FP-624D (46 pages)
- FP-624C (26 pages)
- TP-624D (44 pages)
- TP-624C (25 pages)
- TP-524D-HRT (52 pages)
- TP-524D (40 pages)
- TP-524C (20 pages)
- FP-524D-HRT (52 pages)
- FP-524D Quick Start Guide (2 pages)
- FP-524C (21 pages)
- PI-500 (31 pages)
- TP-424C (15 pages)
- DM-200 (50 pages)
- DM-100 (44 pages)
- FP-100 (34 pages)
- SG1 (16 pages)
- DM-534C (22 pages)
- IR-540 (19 pages)
- IR-522 (19 pages)
- DM-434B (11 pages)
- DM-400IS (22 pages)
- FP-424C (15 pages)