mA line when it is not being used.

Wiring designations are DC+, DC-, and MA (sensor signal).

The

maximum wire length between sensor and 24VDC source is shown in the Table below. The maximum wire
size for termination in the Junction Box is 14 AWG.

Table 1 Wire Gauge vs. Distance

AWG

Wire Dia.

Meters

Feet

Over-Current

Protection

22

0.723mm

700

2080

3A

20

0.812mm

1120

3350

5A

18

1.024mm

1750

5250

7A

16

1.291mm

2800

8400

10A

14

1.628mm

4480

13,440

20A

NOTE 1: Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.

NOTE 2: Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.

NOTE 3: The supply of power should be from an isolated source with over-current protection
as stipulated in table.

NOTE 4: A 250 ohm load resistor is needed on the 4-20 mA line when it is not being used.

Terminal Connections

CAUTION: Do not apply system power to the sensor until all wiring is properly terminated. Refer to
Section 2.8 Initial Start Up.

Customer

Wiring

White

Blue

Yellow

Black

Wiring to

LEL Sensor

Figure 11 Sensor Connector PCB

a) Remove the junction box cover and unplug the Transmitter Module. Identify the terminal blocks for

customer wire connections.

b) Observing correct polarity, terminate the 3-conductor 4-20mA field wiring (DC+, DC-, and MA) to the

sensor assembly wiring in accordance with the detail shown in Figure 11.

c) Trim all exposed wire leads if they are not permanently landed in the terminal block.