Detcon FP-624D User Manual
Page 44

Model FP-624D
FP-624D Instruction Manual
Rev. 1.2
Page 40 of 42
1000 ohms maximum loop load @ 24VDC
0mA
All Fault Diagnostics
2mA
In-Calibration
4-20mA
0-100% full-scale
22mA
Over-range condition
Serial Output:
RS-485 Modbus™ RTU
Baud Rate 9600 BPS (9600, N, 8, 1 Half Duplex)
Relay Outputs:
Alarm 1, Alarm 2, and Fault
5A @ 250VAC
5A @ 30VDC
Status Indicators:
4-digit LED Display with gas concentration, full-script menu
Prompts for AutoSpan, AutoZero, Set-up Options, and Fault Reporting
Faults Monitored:
Loop Fault, Input Voltage Fault, Zero Fault, Sensor Fault,
Processor Fault, Memory Fault, Calibration Fault(s)
4 LEDs for Alarm 1, Alarm 2, Fault, and Calibration
Cable Requirements:
Power/Analog: 3-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG
Serial Output: 2-wire twisted-pair shielded cable specified for RS-485 use
Maximum distance is 4,000 feet to last sensor
Mechanical Specifications
Length:
8 inches (200mm), including Splashguard
Width:
5.5 inches (140mm)
Weight:
2.7lbs (3.4Kg)
Mechanical Connection:
¾” Male NPT threaded connection
Electrical Connection:
Eleven 14 gauge (maximum) wire terminal landings