2 LOCATION - GENERAL

2.11

Access:

For emergencies and maintenance the pump must be

easily

accessible.

2.12

Protection: The pump must be located in a dry position, frost free and

protected from freezing, particularly when installed in a loft (not

recommended).

2.13

Ventilation: Ensure an adequate air flow to cool the pump. Separate

the pump from other appliances that generate heat. An 80 mm (3 “) air

gap must be maintained around the pump.

2.14

Safety: The motor casing can become very hot under normal

operating conditions. Care must be taken to ensure it cannot be

touched during operation.

2.15

Water retention: If possible site the pump in a location where in the

unlikely event of a water leak, any spillage is contained or routed to

avoid electrics or areas sensitive to water damage.

2.16

Static inlet pressure: Before deciding where to locate the unit check to ensure

the static inlet head between pump and cold water level (Figs. 2 & 3) is at least

0.5 metre and does not exceed the max inlet head of 8 metres.

2.17

Pump position: The pump must be positioned on its anti-vibration mounting

feet and as close to the water source as possible. Ensure the pump is mounted

in a position that allows easy access to the box if required.

2.18

Ambient temperature: The pump must be sited in a location where the maximum

ambient temperature does not exceed 40

o

C.

2.19

Pipework: For optimum performance pipework MUST be 22 mm.

Pipework should only reduce to 15 mm when entering terminal fitting.

2.20

Static outlet pressure: The static outlet head (Figs. 2 & 3) must also be within

the maximum requirement of 8 metres.

2.21

Noise: The anti-vibration mounting feet and flexible hoses which are supplied

as standard, and a precaution to reduce noise transmission, however care must

be taken when mounting the pump that any noise is not amplified through loose

panels or pipework.

Do not screw down the pump.

2.22

Flexible hoses: Use only Techflow supplied hoses.

2.23

Isolating valves: Separate isolating valves (non restrictive) must be fitted to

allow easy pump service.

2.24

Pump location: The pump location must be at floor level next to the hot water

cylinder or a level that is below the secondary tapping that feeds the pump. This

will ensure the pump has access to an air free water supply which is important for

trouble free operation, and never more than 4 metres from the hot water cylinder.