Appendixes – MAHLE RTI RHS900 User Manual
Page 48
![background image](/manuals/360606/48/background.png)
- 13.4 -
Appendixes
C:\RHS Computer Files\Instructions\RHS\GB\642-40\0012B-01.doc 1997.09.11
RHS 900
Test - 5:
High pressure
Approx.
19 - 20 bar
Low pressure
Approx.
2.5 bar
Fault/Problem Symptom
Possible
cause
Remedy
Unacceptable
refrigeration
Ice or moisture on
hoses on low
pressure/suction side
of A/C unit
Expansion valve
defective or sensor
placed incorrectly.
Expansion valve opens
too much.
Check expansion
valve sensor
placing.
Replace expansion
valve.
Test - 6:
High pressure
Approx.
7 - 10 bar
Low pressure
Approx.
4 - 6 bar
Fault/Problem Symptom
Possible
cause
Remedy
A/C unit does not
refrigerate
Pressure on low-
pressure side too
high or pressure on
high-pressure side
too low
Internal compressor
leakage
Repair or replace
compressor