10. DESCRIPTION OF ALARM ACTIONS
This chapter describes examples of alarm actions under the following conditions.
Item
Alarm 1
Alarm 2
Parameter
Setpoint
Parameter
Setpoint
Direction of alarm action
E05 : ALM1 ACTION
High-limit alarm
E06 : ALM2 ACTION
Low-limit alarm
Alarm setting
E03 : SET POINT1
80%
E04 : SET POINT2
15%
Hysteresis
E09 : HYSTERESIS1
10%
E10 : HYSTERESIS2
5%
Alarm ON delay
E11 : ON DELAY1
1 sec
E12 : ON DELAY2
3 sec
Alarm OFF delay
E13 : OFF DELAY1
2 sec
E14 : OFF DELAY2
4 sec
Description of
alarm actions
The alarm is output if the condition where
the input value is 80% or more of high-
limit alarm continues for 1 second or
more.
After the alarm is output, when the
condition where the input value is less
than 70% of high-limit alarm continues for
2 seconds or more, the status returns to
normal.
The alarm is output if the condition where
the input value is 15% or less of low-limit
alarm continues for 3 seconds or more.
After the alarm is output, when the
condition where the input value is more
than 20% of low-limit alarm continues for
4 seconds or more, the status returns to
normal.
[%]
0
20
15
40
60
80
100
[1]
[2]
[3]
[4]
1 sec
2 sec
3 sec
4 sec
Alarm-2 hysteresis (5%)
Alarm-1 hysteresis (10%)
Alarm-1 setpoint (80%)
Alarm-2 setpoint (15%)
Elapsed time
1 sec
Alarm-1 ON delay
Alarm-1 OFF delay
Alarm conditions
established
Alarm conditions
established
Normal conditions
established
Normal conditions
established
Low-limit alarm ON
Low-limit alarm OFF
Alarm-2 ON delay
Alarm-2 OFF delay
[1]: Alarm status does not continue for more than 1 second after the
alarm conditions are established at alarm 1.
[2]: Normal status does not continue for more than 2 seconds after the
normal conditions are established at alarm 1.
[3]: Alarm status does not continue for more than 3 seconds after the
alarm conditions are established at alarm 2.
[4]: Normal status does not continue for more than 4 seconds after the
normal conditions are established at alarm 2.
Alarm conditions established
Alarm conditions established
High-limit alarm ON
High-limit alarm OFF
Normal conditions established
Normal conditions established
Alarm-1 action
Alarm-2 action
Alarm
Normal
Normal
Normal
Alarm
Normal