Specification – Yokogawa 414 Batch Controller User Manual
Page 7
2. SPECIFICATION
General
Display:
6 digit LCD. 0.7" (17.8mm) high digits.
Display Update Rate:
0.25 seconds.
Transducer Supply:
8-24VDC field adjustable.
50mA maximum.
Power Requirements:
11.5 to 28.5 volts DC.
130 mA typical current (no options).
AC Mains: Set internally to 95-135 VAC or
190-260 VAC.
Operating Temperature:
0 to 55°C standard.
Dimensions:
5.7" (144mm) wide x 2.8" (72mm) high x
7.0" (178mm) deep.
Cutout:
5.5" (139mm) wide x 2.6" (67mm) high.
Analog Input
Input:
4-20mA, 0-20mA, 1-5 Volt or 0-10 Volt.
The input circuit is floating and isolated from
the power supply and outputs.
Span:
0.1000 to 50000.0000.
Zone:
0.0000 to 50000.0000.
Accuracy:
0.075% of full scale.
Self-Calibrating:
An internal reference is sampled every 10
minutes. Temp Co-efficient is 40ppm/C.
Aging is 20ppm/1000 hrs.
Integration:
The rate is integrated with a timebase
selectable to be in days, hours, minutes or
seconds.
Cut-off:
A cut-off point can be set below which the
rate is not integrated.
Specification 5