5.1 PROGRAMMING THE SETUP PARAMETERS
Step
Display
Description
Text
Ref
1
CAL
BATCH
OPTION
TEST
END
Select the Calibrate mode to setup program
parameters.
Select Batch to enter Batch Setup parameters.
Option (if installed).
Select the test mode to check input signals.
Exit to normal operation.
5.2
5.3
5.4
The following steps are displayed if CAL is selected.
2
RESTOT
Reset all totals to zero.
To reset all totals (resettable and accumulated)
press the BATCH SET key once.
3
INPUT
4-20
0-20
1-5
0-10
Select Input
for 4-20mA.
for 0-20mA.
for 1-5 V.
for 0-10 V.
4
SPAN
xxx.xx
The Span.
Enter the Span.
3.3.1
5
RBASE
xxx
The Zero value.
Enter the Zero base value.
(Normally 0 for most flow applications).
6
PO. n
Lin
Sq. rt.
Op. Ch.
The power of A
n.
Select for linear input (n=1).
Select for square law (n=½).
Select for Open Channel.
3.3.1
If Open Channel is selected Steps 7 and 8 are displayed, otherwise the program
goes to Step 9.
7
POL
Pos
Neg
Polarity.
Flow increases as the input increases.
Flow decreases as the input increases.
8
N
x.xxx
Value of exponent, n.
Program between 0 and 9.999.
3.3.1