Yokogawa 414 Batch Controller User Manual
Page 36
5.2 ENTERING THE BATCH PARAMETERS
Step
Display
Description
Text
Ref
1
BATCH
OPTION
TEST
END
CAL
Enter Batch Parameters.
Option (if installed)
Check Input Signals.
Exit to normal operation.
Program Setup Parameters.
5.3
5.4
5.1
The following steps are displayed if BATCH is selected.
2
BATCH L
xxxxxx
Maximum Batch Size which can be
entered.
Set to 0 if no limit on batch size.
3.2
3
AUTO S
Off
On
xx:xx
Automatic restart feature.
Disable.
Enable.
If enabled, automatically restarts the
batch xx:xx (mins:sec) after the end of
the last batch.
3.2.4
4
START. T
xx:xx
Slow start time.
Time, in (minutes:seconds), when
Relay 2 will energise once the batch
has started.
3.2
5
PREST
xxxx
Prestop Quantity.
Quantity at which Relay 2 will
de-energise before the end of the batch.
(Eg. If the batch quantity is 100 litres
and Prest is 2 litres, relay 2 will
de-energise after 98 litres.)
3.2
34 Calibration