Yokogawa 414 Batch Controller User Manual
Page 40
5.4 CHECKING THE INPUT SIGNAL
Step
Display
Description
Text
Ref
1
TEST
OPTIONS
CAL
BATCH
END
Check the Input Signals.
Options (if installed).
Program Setup Parameters.
Set Batch Parameters.
Exit to normal operation.
5.3
5.1
5.2
The following steps are displayed if TEST is selected.
2
Sr x.xx
Software revision number.
Depending on the input selected, the input current or voltage will be
displayed.
3
4-20mA
xx.xx
Displayed for 1 second followed by the actual
current.
0-20mA
xx.xx
Displayed for 1 second followed by the actual
current.
1-5 Volt
xx.xx
Displayed for 1 second followed by the actual
voltage.
0-10 Volt
xx.xx
Displayed for 1 second followed by the actual
voltage.
If the RS232/422485 option is installed, the display will then show:
4
CLOC
xx:xx:xx
Clock.
Time in Hours:Mins:Sec.
38 Calibration