background image

Starting Out

Watlow VPAC User's Manual

5

Single Phase Wiring

1Ø Wiring for AC & DC Input Contactor
10-40A, Models (CA or CD)

Limit Contactor

Contacts

(if required)

V~(ac) or VDC Input

Command Signal

Depending on Model Ordered

T1

L1

V~(ac)

1Ø Wiring, 4-20mA Burst, 50 & 75A (BL)

L1 L2 T1 T2

Limit Contactor

(if required)

L2

L1

4-20mA

120V~(ac) Fan Power

20 Watts Max. - 75A Only

(Customer Supplied)

Separate Disconnect Required

L2

L1

L1

1Ø Wiring, 4-20mA Burst, 10-40A (BL)

T1

VDC

CD

L2

L1

з

з

з

з

з

WARNING:

1

Wiring must conform to National
Electric Code (NEC) safety standards,
as well as locally applicable codes.
Failure to do so could result in death or
personal injury.

Limit Contactor

Contacts

(if required)

4-20mA

Input

SBL

з

з

з

з

з

WARNING

2

Wiring examples show L2 in 240V~(ac)
or 480 V~(ac) configuration. In
120V~(ac) applications, L2 is neutral and
must not be fused or switched. Failure
to follow this guideline could result in
death or personal injury.

Semiconductor

Fuse

Semiconductor

Fuse

Semi-

conductor

Fuse

1

2

1

2

1