beautypg.com

Specifications, Ordering information, Watlow controls 9 ehg sl10 user’s guide – Watlow Series EHG SL10 Integrated Temperature Controller User Manual

Page 9: Power, No-arc relay, Environmental, Agency approvals, Warranty, 10a switching • 4.5 million cycles, 1998/c-ul

background image

Watlow Controls

9

EHG SL10 User’s Guide

Specifications

Power

• Isolated Universal Power Supply: 85 to 264V

Å (ac)

50/60Hz

• Up to 2400 W with 10A switching capability

NO-ARC Relay

• 10A

switching

• 4.5 million cycles

Environmental

• Ambient operating temperature range 0 to 70 °C (32 to

158 °F)

Agency Approvals

• UL

®

1998/C-UL

®

• CE

60730

• SEMI-S2

Ordering Information

Series EHG SL10 Integrated Temperature Controller
EHG2- CNTL-_ _ _ _

0000 basic control (purchased only as part of a heater assembly)

EHG2- MODU-_ _ _ _

DISP with display module

COMS with communications module

DSCM with display & communications module

Additional Power Cables

4800-0012: jumpered long cable

4800-0022: terminated long cable

4800-0011: jumpered short cable

4800-0021: terminated short cable

Declaration of Conformity

Series EHG SL10

Watlow Winona, Inc.
1241 Bundy Blvd.
Winona, MN 55987 USA

Declares that the following product:
Designation:

Series EHG SL10

Model Numbers:

EHG2-CNTL-(0000, DISP, COMS, DSCM)

Classifi cation:

Electronic Thermostat with Integrated Temperature Limiter Protective

Control, Control Relay = 2CK, Limit Relay = 2JK, TA Relay = 2B

Installation Category II, Pollution degree 2, Software Class B

Rated Supply Source:

100 to 240 V~ (ac), 50 or 60 Hz

IP Code

IP20

Rated Power:

5 VA Unit power, 10 A Resistive Heater Load

Meets the essential requirements of the following European Union Directives by using the relevant
standards show below to indicate compliance.

89/336/EEC Electromagnetic Compatibility Directive

EN 60730-1

2001

+ A1-A4

Automatic electrical controls for household and similar

use

EN 60730-2-9

2002

+ A1

- Temperature Sensing Controls, Class B Emissions

EN 61000-4-2

1996

+ A1, A2

Electrostatic Discharge Immunity

EN 61000-4-3

2006

Radiated Field Immunity

EN 61000-4-4

2004

Electrical Fast-Transient / Burst Immunity

EN 61000-4-5

2006

Surge Immunity

EN 61000-4-6

1996

+ A1, A2, A3 Conducted Immunity

EN 61000-4-8

1994

+ A1

Power frequency magnetic fi eld immunity

EN 61000-4-11

2004

Voltage Dips, Short Interruptions and Voltage

Variations

Immunity

EN 61000-4-28

2000

Variation of power frequency immunity – Level 2

EN 61000-3-2

2006

Harmonic Current Emissions

EN 61000-3-3

2005

Voltage Fluctuations and Flicker

SEMI F47

2000

Specifi cation for Semiconductor Processing Equipment

Voltage Sag Immunity – Figure R1-1

2006/95/EC Low-Voltage Directive

EN 61010-1

2001

Safety Requirements of electrical equipment for mea-

surement,

control and laboratory use. Part 1: General

requirements
EN 60730-1

2001

+ A1-A4

Automatic electrical controls for household and similar

use

EN 60730-2-9

2002

+ A1

- Temperature Sensing Controls

UL 1998

ED.2

Software in programmable components.

Raymond D. Feller III

Winona, Minnesota, USA

Name of Authorized Representative

Place of Issue

General Manager

February 2009

Title of Authorized Representative

Date of Issue

Signature of Authorized Representative

Warranty

The Series EHG SL10 is warranted to be free of defects in material
and workmanship for 24 months after delivery to the first purchaser
for use, providing that the units have not been misapplied. Since
Watlow has no control over their use, and sometimes misuse, we
cannot guarantee against failure. Watlow’s obligations hereunder, at
Watlow’s option, are limited to replacement, repair or refund of pur-
chase price, and parts which upon examination prove to be defective
within the warranty period specified. This warranty does not apply to
damage resulting from transportation, alteration, misuse or abuse.

WARNING: To avoid damage to property and equipment, and/or
injury or loss of life, use National Electric Code (NEC) standard
wiring practices to install and operate the Series EHG SL10. Fail-
ure to do so could result in such damage, and/or injury or death.