beautypg.com

Watlow Series EHG SL10 Integrated Temperature Controller User Manual

Page 5

background image

Watlow Controls

5

EHG SL10 User’s Guide

EHG SL10 Error Codes

Display

Description Possible

Cause

Corrective

Action

[SL1]

Limit error

Sensor has exceeded SLA value or
open thermocouple

Set SLA to correct Safety
Limit Value

Check wiring of sensor

Check sensor confi guration

[SL2]

Control error

Sensor has exceeded SLA value or
open thermocouple

Set SLA to correct Safety
Limit Value

Check wiring of sensor

Check sensor confi guration

[Er3]

Limit Sensor Error

Limit sensor reading out of range (<
-13 or > 640)

Check wiring of sensor

Check sensor confi guration

[Er4]

Control Sensor Error

Control sensor reading out of range
(<-13 or > 640)

Check wiring of sensor

Check sensor confi guration

[Er5]

Limit Ambient Error

Temperature at limit sensor cold junc-
tion (> 185 degrees)

Check to be certain the EHG
SL10 is not in an ambient
condition greater than 185
degrees C

[Er6]

Control Ambient Error

Temperature at control cold junction
(> 185 degrees)

Check to be certain the EHG
SL10 is not in an ambient
condition greater than 185
degrees C

[ER9]

HMI Communications
Fault

Loss of communication between base
and display communications module

Check connection between
EHG SL10 and display/com-
munications module

[Ahi]

Alarm High

Process temp exceeds set point by
value greater than alarm high setting

Set HTA value to correct high
temperature alert value

[Alo]

Alarm Low

Process temp below set point by value
greater than alarm low setting

Set LTA value to correct Low
temperature alert value

[E91]

Communications Queue
Full

Communications buffer overfl ow, re-
turn to factory

Contact Technical Support at
1-507-494-5656

[E10]

EEPROM Error

EEPROM memory space fails CRC
check (checksum for parameter space),
return to factory

Contact Technical Support at
1-507-494-5656

[E11]

CRC Error

Flash memory space fails CRC check
(checksum for program space), return
to factory

Contact Technical Support at
1-507-494-5656

[E12]

CPU Clock Error

Clock frequency is < 5 MHz or > 13.1
MHz, return to factory

Contact Technical Support at
1-507-494-5656

[E13]

Stack Overfl ow

Stack has overfl owed, return to factory

Contact Technical Support at
1-507-494-5656

[E15]

AI Function Error

Analog reference is < 1.82 or > 2.06
volts, return to factory

Contact Technical Support at
1-507-494-5656

[E16]

Process Comparison
Error

Limit and control sensor readings
differ by value greater than process
comparison value

Check setting of Proces Com-
parison Value

Set Process Comparison Value
to correct value

Check wiring of sensors

[E17]

Data Store Error

Data store functions are not set up,
return to factory

Check setting of Proces Com-
parison Value

Check wiring of sensors