EHG SL10 Error Codes
Display
Description Possible
Cause
Corrective
Action
[SL1]
Limit error
Sensor has exceeded SLA value or
open thermocouple
•
Set SLA to correct Safety
Limit Value
•
Check wiring of sensor
•
Check sensor confi guration
[SL2]
Control error
Sensor has exceeded SLA value or
open thermocouple
•
Set SLA to correct Safety
Limit Value
•
Check wiring of sensor
•
Check sensor confi guration
[Er3]
Limit Sensor Error
Limit sensor reading out of range (<
-13 or > 640)
•
Check wiring of sensor
•
Check sensor confi guration
[Er4]
Control Sensor Error
Control sensor reading out of range
(<-13 or > 640)
•
Check wiring of sensor
•
Check sensor confi guration
[Er5]
Limit Ambient Error
Temperature at limit sensor cold junc-
tion (> 185 degrees)
•
Check to be certain the EHG
SL10 is not in an ambient
condition greater than 185
degrees C
[Er6]
Control Ambient Error
Temperature at control cold junction
(> 185 degrees)
•
Check to be certain the EHG
SL10 is not in an ambient
condition greater than 185
degrees C
[ER9]
HMI Communications
Fault
Loss of communication between base
and display communications module
•
Check connection between
EHG SL10 and display/com-
munications module
[Ahi]
Alarm High
Process temp exceeds set point by
value greater than alarm high setting
•
Set HTA value to correct high
temperature alert value
[Alo]
Alarm Low
Process temp below set point by value
greater than alarm low setting
•
Set LTA value to correct Low
temperature alert value
[E91]
Communications Queue
Full
Communications buffer overfl ow, re-
turn to factory
•
Contact Technical Support at
1-507-494-5656
[E10]
EEPROM Error
EEPROM memory space fails CRC
check (checksum for parameter space),
return to factory
•
Contact Technical Support at
1-507-494-5656
[E11]
CRC Error
Flash memory space fails CRC check
(checksum for program space), return
to factory
•
Contact Technical Support at
1-507-494-5656
[E12]
CPU Clock Error
Clock frequency is < 5 MHz or > 13.1
MHz, return to factory
•
Contact Technical Support at
1-507-494-5656
[E13]
Stack Overfl ow
Stack has overfl owed, return to factory
•
Contact Technical Support at
1-507-494-5656
[E15]
AI Function Error
Analog reference is < 1.82 or > 2.06
volts, return to factory
•
Contact Technical Support at
1-507-494-5656
[E16]
Process Comparison
Error
Limit and control sensor readings
differ by value greater than process
comparison value
•
Check setting of Proces Com-
parison Value
•
Set Process Comparison Value
to correct value
•
Check wiring of sensors
[E17]
Data Store Error
Data store functions are not set up,
return to factory
•
Check setting of Proces Com-
parison Value
•
Check wiring of sensors