beautypg.com

Ansi x3.28, Ansi x3.28 "?" command example – Watlow Series 942 Data Communications User Manual

Page 17

background image

How to Use Data Communications

17

WATLOW Series 942

Figure 9 -
ANSI X3.28 "?"
Command Example.

ANSI X3.28 "?"

ANSI X3.28 "?" Command Example

You need to know the Alarm 1 Low value (A1LO). The "?" uses a variation of
the message syntax shown just below. This syntax requires the protocol
start of text and end of text characters.

"?" Command syntax with ANSI X3.28 Protocol:
?

Enter in ASCII:
?
The hex string will be:
023F2041314C4F03

First response from the Series 942:

The hex response string is:
06

Your computer's confirming response:

The response hex string is:
04

Second response from the Series 942:

The hex string is:
023530302003

Your computer's next response:
or < NAK> (if the message needs to be repeated).
The hex string is:
06 or 15

Final response from the Series 942:

The hex string is:
04

Response from the Series 942:

The hex response string is:
06

• You'll find the the complete list of "=" Command arguments (parameters and
value limits) in Table 5, Pages 19 - 21.

5

0

ASCII
Characters

HEX
Value

20

0

0

<

ASCII
Characters

HEX
Value

1

41

4C

31

Space

?

3F 20

A

L

02

03

Optional

Carriage

Return

O

4F