Thermocouple

Figure 3b — Thermocouple wiring.

2- and 3-wire RTD

Figure 3c — 2- and 3-wire RTD wiring.

NOTE: 2- or 3-wire RTD input, calibrated for 0.003850

/

°C curve.

Electromechanical Relay, Form C without contact suppression

10A 103

E - _ _ _ _ - _ 000

Solid-State Relay, Form A, 0.5A without contact suppression

5A 103

K - _ _ _ _ - _ 000

Figure 3d — Electromechanical and solid-state relay wiring.

NOTE: Switching inductive loads (relay coils, solenoids, etc.) with the mechan-
ical relay, switched dc or solid-state relay output options requires use of an
R.C. Suppressor. Watlow carries the R.C. suppressor Quencharc brand name,
which is a trademark of ITW Paktron. Watlow Part No. 0804-0147-0000.

Switched DC

103 C - _ _ _ _ - _ 000

Figure 3e — Switched dc

5

7

6

External

Device

dc -

dc+

dc-

Internal Circuitry

dc+

620

V+

24V

Î

Unregulated

ç

NOTE: We strongly recommend
that all control loops use an
approved temperature limit for
over or under temperature limit
protection.

ç

WARNING: Failure to install a
temperature limit for protection
where a potential hazard exists
could result in damage to equip-
ment and property wiring and
injury to personnel.

L1

Fuse

L2

5

NC

External

Device

NO

7

C

9

Output Wiring

10 11 12

S1

S2

S3

3-wire RTD

10 11

S1

S2

S3

12

2-wire RTD

TC+

TC-

10 11

Input Wiring

3

Watlow Series 103 User’s Manual

120VÅ

103_ - 1 _ _ _ - 0000

230 to 240VÅ

103_ - 2 _ _ _ - 0000

NOTE: The line voltage is specified by your model number.

ç

WARNING: To avoid potential electric shock, use National Electrical
Code safety practices when wiring and connecting this unit to a
power source and to electrical sensors or peripheral devices.
Failure to do so could result in injury or death.

All wiring and fusing must conform to the National Electric

Code and to any locally applicable codes.

ç

CAUTION: Applying incorrect voltage may result in irreversible
damage to the control.

Figure 3a — Power wiring.

15

L1

Fuse

L2

1

3

Recommended

fuse size: 1A

Power Wiring