Watlow Series 103 User Manual
Series 103, User’s manual, On/off temperature controller
1
■
Watlow Series 103 User’s Manual
(2001)
Control Mode
• On-off
• Nominal switching hysteresis, typically 3°F (1.7°C)
Operator Interface
• LED indication of output status
• Dial scale calibrated to compensate for sensor non-linearities
• Integral set point
• Dual temperature scale (°F and °C)
• Fixed set point
• Manufactured to specified value
Input
• Thermocouple or platinum RTD available
• Thermocouple with automatic cold junction compensation
• Thermocouple may be isolated or grounded
• Thermocouple and RTD break protection de-energizes output
• 2- or 3-wire RTD input, 100
Ω
, 500
Ω
or 1000
Ω
@ 0°C calibrated
for 0.003850
Ω
/
Ω
°C curve, factory selectable
Output
• Solid-state relay, Form A, 0.5A @ 24V~ min., 264V~ maximum,
opto-isolated, zero cross switching
• Switched dc signal provides a non-isolated minimum turn-on volt-
age of 3V
Î
(dc) into a minimum 500
Ω
load, maximum on voltage
not greater than 32V
Î
(dc)
• Electromechanical relay, 8A, Form C, SPDT: 8A @ 240V~ resis-
tive, 8A, 28V
Î
(dc) resistive, 275 VA pilot duty rated
Accuracy
Adjustable Set Point
• Calibration accuracy: ±1% of span, at 77°F ±5°F (25°C ± 3°C)
ambient and rated line voltage ± 1%
• Set point accuracy: ±3% of dial scale
• Accuracy span: 1000°F (540°C) minimum
Fixed Set Point
• Calibration accuracy: ±10°F/±6°C of setting, at 77°F ±5°F (25°C
±3°C) ambient and rated line voltage ±1%
Temperature Stability
• Thermocouple: Typically 5µV/°F ambient (9µV/°C ambient) input
referenced
• RTD: Typically 0.2°F/°F ambient (0.2°C/°C ambient)
Voltage Stability
• ±0.01% of span (min span of 1000°F or 540°C) per % of rated
line voltage
Agency Approvals
• CE: EN61010 - Safety
EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2
•
873, File #E43684
•
to C22.2 No. 24, File #E43684
• Approved for use in commercial cooking applications
Terminals
• Captive screw, cage clamp connection, 0.155 in. (4mm) max.
width screwdriver blade, 30 to 14-gauge wire
Mounting
• DIN rail, DIN EN50022, 35mm x 7.5mm
• Sub-panel mounting
Power
• 120V~, +10%/-15%, 50/60 Hz
• 230V~ to 240~, +10%/-15%, 50/60 Hz
• 10VA maximum power
Operating Environment
• 32 to 131°F (0 to 55°C)
• 0 to 90% RH, non-condensing
• Storage temperature: -4 to 185°F (-20 to 85°C)
Dimensions
• Width: 2.28 in (60 mm)
• Height: 4.45 in (115mm)
• Depth: 3.89 in (100 mm)
Weight
• 0.7 lb. (0.3kg)
UL® is a registered trademark of Underwriter’s Laboratories, Inc.
Note: Specifications subject to change without notice.
User’s Manual
On/Off Temperature
Controller
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com
TOTAL
3 Year Warranty
CUSTOMER
SATISFACTION
0600-0004-0007 Rev D
January 2001
Supersedes: 0600-0004-0007 Rev C
$5.00 Made in the U.S.A.
Printed on Recycled Paper
10% Postconsumer Waste
The Watlow Series 103 is a DIN rail mount, on-off
temperature controller with a thermocouple or RTD
sensor input. The DIN rail mounting offers quick and
easy installation with the use of simple hand tools. The
controller may also be flush mounted.
The Series 103 can be factory configured as either a
heat or cool output. Output types include electromechani-
cal relay, solid-state relay or open collector output.
The Series 103 has an LED for output status
indication and can be ordered with an integral, adjustable
set point or a fixed set point.