Figure 2a — Series 103 dimensions.

Sub-Panel Mounting the Series 103

1. Using the controller as a location template, mark both

mounting holes.

2. Drill two 0.19 in. (5mm) diameter holes in the desired

panel location. See Figure 2a for hole locations.

3. Mount the Series 103 using two #8-32 screws.

DIN Rail Mounting the Series 103

1. Place the Series 103 upper mounting clip on the top edge

of the DIN rail. See the Figure 2b on this page.

2. Press down firmly on the top front edge of the Series 103.

The control “snaps” securely onto the rail. If the control
does not snap on, check to see if the DIN rail is bent.
Minimum clipping distance is 1.37 in. (34.8mm), the
maximum is 1.39 in. (35.3mm).

Removing the Series 103 from the DIN Rail

1. Place your fingers on the release lever located at the base

of the Series 103.

2. While gently pressing on the top of the case, above

Terminals 1 to 9, pull forward on the release lever.

Note, caution and warning symbols appear throughout this
book to draw your attention to important operational and
safety information.

A “NOTE” marks a short message to alert you to an impor-
tant detail.

A “CAUTION” safety alert appears with information that is
important for protecting your equipment and performance.

A “WARNING” safety alert appears with information that is
important for protecting you, others and equipment from
damage. Pay very close attention to all warnings that apply
to your application.

The ç symbol (an exclamation point in a triangle) precedes
a general CAUTION or WARNING statement.

The Ó symbol (a lightning bolt in a triangle) precedes an
electric shock hazard CAUTION or WARNING safety
statement.

Figure 2b — Series 103 side view mounting.

• Use the correct sensor type per the model number on the

unit sticker.

• Use the proper thermocouple or RTD polarity.

• Insulate the thermocouple mounting from the mounting

surface to prevent heat migration input errors.

• Thermocouple leads should be twisted pair wire and

routed separately from any other lines.

• In electrically noisy environments (heavy switching of

contactor, motors, solenoids, etc.) use shielded thermocou-
ple lead wire with the shield connected at the sensor end
only.

• All wiring and fusing must conform to the National

Electric Code (NEC) NFPA70 and any other locally applic-
able codes.

• Fuse the independent load voltage on the L1 (hot) side

and connect it to the common (COM) side of the relay.

ç

CAUTION: A power disconnect switch located near the controller
is recommended to shut down power in case of controller
failure.

• Long lead lengths create electrical resistance. When using

a two-wire RTD, there will be an additional error for
every 1

of lead length resistance. That resistance when

added to the resistance of the RTD element, can result in
erroneous input to the temperature controller. To over-
come this problem, use a three-wire RTD sensor, which
compensates for lead length resistance. When extension
wire is used for a three-wire RTD, all three extension
wires must have the same electrical resistance (i.e. same
gauge, copper stranded).

Wiring Guidelines

DIN Rail

Panel

Upper Mounting Clip

Lower Mounting Clip

Snap Action

Release Lever

Mounting

Safety Information

Installation

3.89 in.

(99mm)

3.72 in.

(95mm)

2.28 in.

(58mm)

1.62 in.

(41mm)

4.45 in.

(113mm)

35mm x 7.5mm

Rail is not

included in

the assembly

4.10 in.

(104mm)

3.75 in.

(96mm)

Dimensions

2

Watlow Series 103 User’s Manual