V~ (ac) – Watlow DIN-A-MITE Style B User Manual

Page 9

background image

WATLOW DIN-A-MITE Style B User's Manual

9

NOTE: The current transformer must be in the center uncontrolled leg on a 2-leg DIN-A-MITE.

Non-latching Alarm Option
(models DB_ _ -

_ _ _ _

- S _ _ _ )

Shorted SCR (silicon-controlled rectifier) Alarm
Non-latching Operation

The shorted SCR detector compares the input
command signal and actual load current. If load
current is present without an input signal then the
shorted SCR alarm will energize the alarm triac
output. This is a non-latching alarm. This output can
be used to drive various indication devices, such as a
coil, light, buzzer, etc. See the alternative latching
circuit section below.

V

Å

13

14

Triac

RY1
Coil

Reset Switch

RY1A

L1

L2

RY1B

Normally open

Common

Normally closed

(External alarm relay
contacts, set A)

(External alarm relay
contacts, set B)

Latching Alarm Relay Circuit

Ungrounded Delta or Wye Load

3-phase, 2-leg DIN-A-MITE

Current

Transformer (CT)

Delta
Load

Ungrounded

Wye Load

6

5

4

V~

(ac)

120 or 240V~ (ac)
@ 300mA maximum
energizes on alarm

Semiconductor

Fuses

Signal

Alarm Relay

or Indicator

1A

7
8
9

10
11
12
13
14
15
16

1 2 3

4 5 6

High-limit

Contactor (CR1)

CT

DB20-60C0-S000

NOTE:
Use a grounding conductor
terminal plate (fork
terminal) having upturned
lugs or the equivalent to
hold the wire in position.
Maximum 6 mm

2

(10 AWG)

wire.