Pvm - pg24 – Poly-Tex Poly-Vent (Retrofit) User Manual
Page 24
24
Q. How much time does it take to inflate and/or deflate the Poly-Vent?
A. The length of time necesary to inflate or deflate the Poly-Vent is variable depending on several factors. Length of
Poly-Vent, height of Poly-Vent, and the number and location of the blowers connected to the Poly-Vent. Obviously,
the longer the Poly-Vent, the more time is necessary to inflate and deflate. The same applies to different Poly-Vent
heights. A Poly-Vent II (single stage) system will take more time to inflate or deflate than a Poly-Vent III (two-stage)
system due to the fact that all the air must pass through more tubes and enter and exit through just one blower.
F.A.Q.
Blower fan does not rotate
No power to motor
Check power source (most often the cicuit panel).
Obstruction in blower
Turn off power source and check blower for debris.
Damaged blower
Replace the blower.
Thermostat set too high
Adjust the thermostat to a lower temperature.
Blower "hums" but fan does
Incorrect voltage
Check power source for correct voltage.
not rotate
Obstruction in blower
Turn off power source and check blower for debris.
Blower fan rotates but
Faulty flex tube
Check flex tube for damage or obstructions.
Poly-Vent does not inflate
Poor flex tube connection(s)
Check connection around air transfer gaskets for leaks.
Poly-Vent does not inflate
Air leaking somewhere in the
Check for holes or tears in Poly-Vent and repair with
completely
Poly-Vent
Poly Patch tape.
Water accumulation in Poly-Vent
If water should accumulate, it might accumulate in just
one of the tubes. Make a 1/2" to 1" slit where the water
has accumulated and drain the water. Repair the slit
with Poly Patch tape.
Poly-Vent III only:
Thermostat not wired correctly
Remove pink wire from the thermostat to the top
Top blower shuts off before
to blower motor
blower motor and attach to the lower blower motor.
the bottom blower
Remove the red wire from the lower blower motor and
attach to the top blower motor.