INSTALLATION

POWER WAVE

®

R350

A-1

TECHNICAL SPECIFICATIONS - POWER WAVE

®

R350

RECOMMENDED INPUT WIRE AND FUSE SIZES

1

INPUT

VOLTAGE / PHASE/

FREQUENCY

200-208/1/50/60
200-208/3/50/60

230/1/50/60
230/3/50/60

380-415/1/50/60
380-415/3/50/60

460/1/50/60
460/3/50/60
575/1/50/60

575/3/50/60

TIME DELAY FUSE

OR BREAKER

2

AMPERAGE

80
50
80
45
50
30

45
25
35

20

CORD SIZE

3

AWG SIZES

(mm

2

)

6 (13)
8 (10)

4 (16)
8 (10)
8 (10)

12 (4)
8 (10)

12 (4)
10 (6)

14 (2.5)

MAXIMUM

INPUT AMPERE RAT-

ING AND DUTY CYCLE

60A, 100%
39A, 40%

67A, 30%
35A, 40%
38A, 40%
19A, 40%

34A, 40%
17A, 40%
27A, 40%

14A, 40%

RATED OUTPUT

POWER SOURCE-INPUT VOLTAGE AND CURRENT

Model

K3022-1

Duty Cycle

40% rating

100% rating

300 Amps

29 Volts

350 Amps

31.5 Volts

320 Amps

30 Volts

INPUT

VOLTAGE/PHASE/

FREQUENCY

200-208/1/50/60

230/1/50/60*

200-208/3/50/60

230/3/50/60

380-415/3/50/60

460/3/50/60
575/3/50/60

Input Amperes

(1 Phase in parenthesis)

39/35/19/17/14

(60/67*/NA/NA/NA)

31/28/15/14/11

(60/53/NA/NA/NA)

Idle Power

300 Watts Max.

(fan on)

Power Factor @

Rated Output

.95

Input Voltage ± 10%

208/230/380-415/460/575

50/60 Hz

1. Based on U.S. National electrical Code

2. Also called " inverse time" or "thermal / magnetic" circuit breakers; circuit breakers that have a delay in trip-

ping action that decreases as the magnitude of the current increases

3. Type SO cord or similar in 30° C ambient

4. When operating on these inputs, the line cord should be changed to an input conductor of 6 AWG or larger.

* On 230 Volt / 1 phase inputs the max. rating is at a duty cycle of 30%, except for GTAW processes.

GMAW

40%

60%

100%

300 Amps / 29 Volts

300 Amps

22 Volts

350 Amps

24 Volts

325 Amps

23 Volts

GTAW-DC

40%

60%

100%