beautypg.com

Operation, Auxiliary power operation, Warning – Lincoln Electric IM10073 OUTBACK 145 User Manual

Page 21

background image

B-7

OPERATION

B-7

OUTBACK™ 145

®]

TABLE B.2

ELECTRODE SELECTION GUIDE

120V Receptacle Operation:

• Set the Output Control on the Pro-Cut 25 no higher

than the 15 amp position.( Higher settings may cause
circuit breaker on the OUTBACK™ 145 to trip.)

• Maximum material thickness that can be cut is 1/4".

240V Receptacle Operation:

• The Pro-Cut 25 may be used for its full range of con-

trol.

• Maximum material thickness that can be cut is 3/8".

AUXILIARY POWER OPERATION

Be sure that any electrical equipment plugged into
the generator AC power receptacles can withstand
a ±10% voltage and a ±5% frequency variation.
Some electronic devices cannot be powered by
the OUTBACK™ 145 Refer to Table A.2, ELECTRI-
CAL DEVICE USE WITH THE OUTBACK™ 145, in
the INSTALLATION section of this manual.

-------------------------------------------------------------

GENERAL INFORMATION

The OUTBACK™ 145 is rated at 4750 Peak watts or
4250 continuous watts. It provides both 120 volt and
240 volt power. You can draw up to 20 amps from
either side of the 120 volt duplex receptacle, but not
more than 35.4 amps from both sides at once. Up to
17.7 amps can be drawn from the single 240 volt
receptacle.

WARNING

CURRENT RANGE (AMPS)

AWS

ELECTRODE

CLASSIFICATION

ELECTRODE TYPE

POLARITY

3/32 SIZE

1/8 SIZE

5/32 SIZE

E6010

FLEETWELD® 5P

DC+

50-75

75-135

-

E6011

FLEETWELD® 35

DC+

50-75

70-110

80-125

E6011

FLEETWELD® 180

DC+

50-80

55-110

105-125

E6013

FLEETWELD® 37

DC±

70-95

100-135

-

E7018

EXCALIBUR® 7018

DC+

70-100

90-125

125-145

E7018

JETWELD® LH-73

DC+

65-85

90-125

-

E708-17 & E308L-17 BLUE MAX® 308/308L AC-DC

DC+

50-80

75-110

80-125

ENi-CI

SOFTWELD® 99Ni

DC+

50-80

80-110

-

-

WEARSHIELD® ABR

DC+

-

50-150

-

1/8 AND

SHEET THICKNESS

THINNER

1/8 AND THICKER

Electrical loads in watts are calculated by multiplying
the voltage rating of the load by the number of amps it
draws. (This information is given on the load device
nameplate.) For example, a device rated 120 volts, 2
amps will need 240 watts of power (120 x 2 = 240).

You can use Table B.3, AUXILIARY POWER APPLI-
CATIONS, to determine the wattage requirements of
the most common types of loads you can power with
the OUTBACK™ 145 Be sure to read the notes at the
bottom of the table.

TO USE THE OUTBACK 145 AS AN AUXILIARY
POWER SUPPLY:

1. Start the gasoline engine. See ENGINE OPERA-

TION in this section of the manual.

2. Set the current control dial on the output control

panel to “MAX.” See Figure B.1.

3. Plug the load(s) into the appropriate 120 volt or

240 volt power receptacle.

NOTE: During welding, the maximum generator out-

put for auxiliary loads is 100 watts.

NOTE: You can supply multiple loads as long as the

total load does not exceed 4750 Peak watts
or 4750 continuous watts. Be sure to start the
largest loads first.