Installation, Technical specifications – Lincoln Electric IM10132 FLEXTEC 650 User Manual

Page 7

background image

FLEXTEC™ 650

A-1

INSTALLATION

A-1

TECHNICAL SPECIFICATIONS -

FLEXTEC™ 650

RATED OUTPUT*

POWER SOURCE-INPUT VOLTAGE AND CURRENT

Model

K3060-2

Duty Cycle

60% rating

100% rating

Volts at Rated Amperes

44V

34V

44V

Amperes

750

650

750

650

750

650

750

650

750

650

750

650

Duty Cycle

60%

100%

60%

100%

60%

100%

60%

100%

60%

100%

60%

100%

Process

GMAW (CV)

GTAW (CC)

SMAW (CC)

FCAW-GS (CV)

FCAW-SS (CV)

SAW (CV)

Input Amperes

61 / 50 / 40

57 / 47 / 38

Idle Power

(W)

230 MAX.( Fan On)

100 MAX. (Fan Off)

Power Factor @

Rated Output

88%

Input Voltage ± 10%

380 / 460 / 575 / 3 / 50 / 60

(1) Cord and Fuse Sizes based upon the U.S. National Electric Code and maximum output for 40°C (104°) ambient.
(2) Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers that have a delay in tripping action that decreases as the

magnitude of current increases.

(3) Type SJ cord or similar in 30°C ambient.

VOLTAGE

50/60Hz

380/3/50
460/3/60
575/3/60

Maximum

Input

Amperes

70 A
58 A
46 A

Cord Size

(3)

AWG SIZES

(mm)

4(25)
4(25)
6(16)

Fuse (Super Lag) or

Breaker Size

(2)

90
80
60

COPPER GROUNDING

CONDUCTOR

AWG (mm

2

)

8 (10)
8 (10)
10 (6)

Type 75°C Copper

Wire in Conduit

AWG (mm

2

)

4(25)
6(16)

8 (10)

RECOMMENDED INPUT WIRE AND FUSE SIZES

(1)

*

*

*

*

*

*

*

*

*

*

*

Output is limited to 600A / 100% and 700A / 60% when used with K3091-1 Multi-Process Switch.