beautypg.com

Vanguard EZCT-2000 User Manual

Page 26

background image

EZCT-2000 USER’S MANUAL

REV 3

22

Table 3. Descriptions of Tabulated Test Results Elements

Item

Number

Description

1

Test record header information.

2

The EZCT-2000 X terminals (taps) that were selected for this test.

3

Test note for this particular test. The test note can be up to 20-characters long.

4

Recorded excitation current readings on the CT secondary winding.

5

Recorded excitation test voltages applied to the CT secondary winding.

6

Impedance calculated at each data point.

7

The voltage, current, and impedance data points recorded on the graph grid-marks.

8

Measured DC resistance value of CT under test.

9

ASA 10/50 knee point voltage and excitation current
(This is equivalent to the IEC 10/50 and ANSI 10/50 knee point voltage and excitation current)

10

IEEE 30

° knee point voltage and excitation current.

11

IEEE 45

° knee point voltage and excitation current.

12

CT nameplate turns ratio.

13

Measured turns ratio.

14

Turns ratio percentage error.

15

Polarity of the CT.

16

Measured phase angle.

17

Excitation voltage used in CT turns ratio test.

18

Excitation current in turns ratio test.

19

Current ratio error table. This information will be printed only if you selected “YES” for the “CALC ERR
VS BURDEN?” option when running a test. See section 3.3.2, step h for details.