Vanguard CT-7500 S2 User Manual
Page 54

CT-7500 S2 USER’S MANUAL
REV 2
49
c. The following screen will be displayed:
Press the
[1]
key (WINDOW = 1 SEC).
NOTE
The 1-second timing window is used for breaker timing. The 10 and 20-
second timing windows are used for long timing events such as for timing
circuit-switchers.
d. The following screen will be displayed:
Press the
[1]
key (INTERNAL TRIGGER).
e. The following screen will be displayed:
Press the
[1]
key (OPEN).
f. The following screen will be displayed:
Hold down the
[ARM]
switch and press the
[START]
key.
g. The following screen will be displayed:
Continue to hold down the
[ARM]
switch until testing is finished. You will be returned
to the “START-UP” menu once testing is finished.
TEST IN PROGRESS
Hold “ARM” until
test completes.
(Up to 25 seconds)
Hold “ARM” until
test completes.
“START” to Begin
“STOP” to ABORT
TIMING MODE:
1. OPEN 2. CLOSE
3. O-C 4. C-O
5. O-C-O
TRIGGER MODE:
1. INTERNAL TRIGGER
2. EXTERNAL TRIGGER
TIMING WINDOW:
1. WINDOW = 1 SEC
2. WINDOW = 10 SEC
3. WINDOW = 20 SEC