beautypg.com

Vanguard CT-7500 S2 User Manual

Page 10

background image

CT-7500 S2 USER’S MANUAL

REV 2

5

1.2 Technical

Specifications

Table 1. CT-7500 S2 Technical Specifications

TYPE Portable circuit-breaker analyzer

PHYSICAL SPECIFICATIONS 16”W x 11”H x 14”D (40.6 cm x 29.9 cm x 35.6 cm); Weight: less than 25 lbs (11.3 kg)

INPUT POWER

100 – 120 Vac or 200 – 240 Vac (selectable), 50/60Hz

DRY-CONTACT INPUTS 3, 6 or 12 dry-input channels (depending on model). Each channel detects main and

insertion-resistor contacts

TIMING WINDOWS 1-second, 10-seconds, or 20-seconds

TIMING RESOLUTIONS ±50 micro-seconds @ 1-second duration,

±500 micro-seconds @ 10-second duration,
±1.0 milli-seconds @ 20-second duration

TIMING ACCURACY 0.05% of reading ±0.05 ms @ 1-second duration

DRY-CONTACT CHANNEL

PROTECTION

All contact inputs are grounded until test; input channels are protected against static
discharge

DRY-CONTACT DETECTION

RANGE

Closed: less than 20 ohms;
Open: greater than 5,000 ohms

RESISTOR DETECTION RANGE 50 – 5,000 ohms

CT CURRENT SENSOR One, non-contact, 0 – 100 Amperes

TRIGGER INPUT VOLTAGE Open/Close: 30 – 300V, DC or peak AC

VOLTAGE SENSING INPUT

RANGE

V1: analog input; 0 – 255V DC or peak AC; Sensitivity ±1V
V2: voltage presence/absence detector input; 30 – 300V DC or peak AC

BREAKER OPERATIONS Initiate Open, Close, Open– Close, Close – Open, Open – Close – Open

BREAKER INITIATE CAPACITY 30A, 250Vac/dc max

INITIATE CURRENT READING

RANGE

One, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz

DIGITAL TRAVEL TRANSDUCER

INPUTS

3 digital travel transducer channels; Linear range, 0.0 – 60.0 in (±0.01 in); Rotary
range: 0 – 360 degrees (±0.36 degrees)

RESISTOR TYPE TRANSDUCER

INPUT

200 Ohms – 10K Ohms

CONTACT TRAVEL POINT

DIFFERENCE

Measures “slow-close” contact-point distances; results can be printed

DISPLAY

Back-lit LCD Screen (20 characters by 4 lines); viewable in bright sunlight and low-light
levels

PRINTER Built-in 4.5-inch wide thermal printer can print both graphic contact travel waveforms

and tabulated test results

INTERNAL TEST RECORD

STORAGE

Stores up to 150 test records and 99 test plans

COMPUTER INTERFACES One RS-232C port, One USB port

PC SOFTWARE Windows

®

XP/Vista-based Breaker-Analysis software is included with purchase price

SAFETY Designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards

ENVIRONMENT Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)

HUMIDITY (MAX)

90% RH @ 40˚ C (104˚ F) non-condensing

ALTITUDE (MAX)

2000m (6562 ft) to fully safety specifications

OPTIONS

Transportation case (available for the CT-7500 S2 and the travel transducers)

WARRANTY One year on parts and labor

NOTE

The above specifications are valid at nominal operating voltage and at a
temperature of 25

°C (77°F). Specifications may change without prior notice.