LEESON SM-Plus Series Sub-Micro Inverters User Manual
Page 34

30
FACTORY
NO.
PARAMETER NAME
RANGE OF ADJUSTMENT
DEFAULT
(NOTE 1)
27
BASE FREQUENCY
25.0 - 500.0 Hz (NOTE 4)
60.0 Hz
28
FIXED BOOST
0.0 - 30.0 %
1.0 %
29
ACCEL BOOST
0.0 - 20.0 %
0.0 %
30
SLIP COMPENSATION
0.0 - 5.0 %
0.0 %
31-37
PRESET SPEEDS
0.0 - MAXIMUM FREQUENCY
0.0 Hz
38
SKIP BANDWIDTH
0.0 - 10.0 Hz
0.0 Hz
39
SPEED SCALING
0.0 - 6500.0
0.0
40
FREQUENCY SCALING
3.0 -2 000.0 Hz
60.0 Hz
41
LOAD SCALING
10 - 200 %
200 %
42
ACCEL / DECEL #2
0.1 - 3600.0 SEC
20.0 SEC
43
SERIAL ADDRESS
1 - 247
1
44
PASSWORD
000 - 999
225
47
CLEAR HISTORY
MAINTAIN (01), CLEAR (02)
MAINTAIN (01)
48
PROGRAM
USER SETTINGS (01), OEM SETTINGS (02),
USER
SELECTION
RESET OEM (03), RESET 60 (04),
SETTINGS (01)
RESET 50 (05), TRANSLATE (06)
50
FAULT HISTORY
(VIEW - ONLY)
(N/A)
51
SOFTWARE CODE
(VIEW - ONLY)
(N/A)
52
DC BUS VOLTAGE
(VIEW - ONLY)
(N/A)
53
MOTOR VOLTAGE
(VIEW - ONLY)
(N/A)
54
LOAD
(VIEW - ONLY)
(N/A)
55
0 - 10 VDC INPUT
(VIEW - ONLY)
(N/A)
56
4-20 mA INPUT
(VIEW - ONLY)
(N/A)
57
TB STRIP STATUS
(VIEW - ONLY)
(N/A)
58
KEYPAD STATUS
(VIEW - ONLY)
(N/A)
59
TB-30 OUTPUT
(VIEW - ONLY)
(N/A)
60
TB-31 OUTPUT
(VIEW - ONLY)
(N/A)
NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base
frequency.
NOTE 4: Maximum setting is 1300.0 Hz (factory default is 999.9) on drives with High Output
Frequency option. Consult the factory.
PARAMETER MENU (cont)