LEESON SM-Plus Series Sub-Micro Inverters User Manual
Page 15

7.2
INPUT FUSING AND DISCONNECT REQUIREMENTS
A circuit breaker or a disconnect switch with fuses must be provided in accordance with the National
Electric Code (NEC) and all local codes. Refer to the following table for proper fuse/circuit breaker
rating and wire size.
11
INPUT FUSE / CIRCUIT BREAKER RATINGS AND WIRE SIZE REQUIREMENTS (Note 1)
208/240 Vac, 1 phase
208/240 Vac, 3 phase
400/480 Vac, 3 phase
480/490 Vac, 3 phase
Catalog
Fuse Rating
Wire Size
Catalog
Fuse Rating
Wire Size
Catalog
Fuse Rating
Wire Size
Catalog
Fuse Rating
Wire Size
HP
Number
Note(2)
AWG (mm
2
)
Number
Note(2)
AWG (mm
2
)
Number
Note(2)
AWG (mm
2
)
Number
Note(2)
AWG (mm
2
)
0.25 174452
10A
14(1.5) 174452
10A
14(1.5)
0.5
174453
10A
14(1.5) 174453
10A
14(1.5)
174459
10A
14(1.5)
1
174454
15A
12(1.5)
174454
10A
14(1.5)
174460
10A
14(1.5)
174464
10A
14(1.5)
174455
1.5
174493
20A
12(2.5)
174493
12/10A
14(1.5)
174461
10A
14(1.5)
174456
2
174494
25/20A
10(2.5)
174494
15/12A
12(2.5)
174462
10A
14(1.5)
174491
10A
14(1.5)
174457
3
174495
30/25A
10(4.0)
174495
20/15A
10(4.0)
174463
10A
14(1.5)
174497
10A
14(1.5)
174458
5
174444
45/40A
10(6.0)
174444
30/25A
8(6.0)
174447
15A
14(1.5)
174448
12A
14(1.5)
174446
7.5
174438
45/40A
8(6.0)
174440
20A
12(2.5)
174442
20A
14(1.5)
10
174439
50/50A
8(10)
174441 30/25A
10(4.0)
174443
20A
12(2.5)
15
174429
80/75A
6(16)
174431 40/35A
8(6.0)
174434
30A
10(4.0)
20
174430 100/90A
4(25)
174432 50/45A
8(10)
174435
40A
8(6.0)
25
174433 70/60A
6(16)
174436
45A
8(6.0)
30
174500 80/70A
6(16)
NOTE 1: Applicable national and local electrical codes take precedence over recommendations in this table.
NOTE 2: Use UL Class CC or Class T fast-acting, current limiting type fuses. Select fuses with low I
2
T values, rated at
200,000 AIC. Recommended fuses are Bussman KTK-R, JJN, and JJS. Similar fuses with equivalent ratings by other
manufacturers may also be acceptable.