WARNING:
Control terminals are not isolated from line voltage! Do not touch!
Storage Temperature
-20 to 70 C
Ambient Operating Temperature
0 to 50 C (up to 6 kHz carrier, derate above 6 kHz)
Ambient Humidity
< 95% (non-condensing)
Altitude
3300 ft (1000 m) above sea level (without derating)
Input Line Voltages
120/208/240 Vac single phase, 208/240 Vac three phase
Input Voltage Tolerance
+10%, -15%
Input Frequency Tolerance
48 to 62 Hz
Output Wave Form
Sine Coded PWM
Output Frequency
0 - 99 Hz
Carrier Frequency
4 kHz to 10 kHz
Service Factor
1.00 (up to 6 kHz carrier, derate above 6 kHz)
Efficiency
Up to 98%
Power Factor (displacement)
0.96 or better
Overload Current Capacity
150% for 60 seconds, 180% for 30 seconds
Speed Reference Follower
Speed Potentiometer, 0-10 VDC (must be isolated)
1
Power Supply for Auxiliary Relay
50 mA at 12 VDC
Digital Output
Circuit rated 50 mA and 30 VDC max (to drive auxiliary relay)