beautypg.com

LEESON SM-Basic Series Sub-Micro Inverters (Obsolete) User Manual

Page 7

background image

3

3.0

SM-Basic MODEL DESIGNATION CODE

4.0

SM-Basic SPECIFICATIONS

1

WARNING:

Control terminals are not isolated from line voltage! Do not touch!

Storage Temperature

-20 to 70 C

Ambient Operating Temperature

0 to 50 C (up to 6 kHz carrier, derate above 6 kHz)

Ambient Humidity

< 95% (non-condensing)

Altitude

3300 ft (1000 m) above sea level (without derating)

Input Line Voltages

120/208/240 Vac single phase, 208/240 Vac three phase

Input Voltage Tolerance

+10%, -15%

Input Frequency Tolerance

48 to 62 Hz

Output Wave Form

Sine Coded PWM

Output Frequency

0 - 99 Hz

Carrier Frequency

4 kHz to 10 kHz

Service Factor

1.00 (up to 6 kHz carrier, derate above 6 kHz)

Efficiency

Up to 98%

Power Factor (displacement)

0.96 or better

Overload Current Capacity

150% for 60 seconds, 180% for 30 seconds

Speed Reference Follower

Speed Potentiometer, 0-10 VDC (must be isolated)

1

Power Supply for Auxiliary Relay

50 mA at 12 VDC

Digital Output

Circuit rated 50 mA and 30 VDC max (to drive auxiliary relay)

1