LEESON SM Series Sub-Micro Inverters User Manual
Page 31

FACTORY
NO.
PARAMETER NAME
RANGE OF ADJUSTMENT
DEFAULT
12
TB-13E FUNCTION
NONE (01), 0-10 VDC (02), 4-20mA (03),
NONE (01)
SELECT
PRESET SPEED #3 (04), INCREASE FREQ (05),
START FORWARD (06), EXTERNAL FAULT (07),
INVERSE EXT FAULT (08), AUXILIARY STOP (09),
ACCEL/DECEL #2 (10).
TB-13E OUTPUT
RUN (11), FAULT (12), INVERSE FAULT (13),
SELECTIONS
FAULT LOCKOUT (14), AT SET SPEED (15),
ABOVE PRESET #3 (16), CURRENT LIMIT (17),
AUTO SPEED (18), REVERSE (19),
DYNAMIC BRAKING (20),
OTHER SELECTIONS
REMOTE KEYPAD (21)
14
CONTROL
TERMINAL STRIP ONLY (01),
TERMINAL STRIP
REMOTE KEYPAD ONLY (02),
ONLY (01)
16
UNITS EDITING
TENTHS OF UNITS (01),
WHOLE
WHOLE UNITS (02)
UNITS (02)
17
ROTATION
FORWARD ONLY (01),
FORWARD
FORWARD AND REVERSE (02)
ONLY (01)
19
ACCELERATION TIME
0.1 - 3600.0 SEC
20.0 SEC
20
DECELERATION TIME
0.1 - 3600.0 SEC
20.0 SEC
21
DC BRAKE TIME
0.0 - 3600.0 SEC
0.0 SEC
22
DC BRAKE VOLTAGE
0.0 - 30.0 %
0.0 %
23
MINIMUM FREQUENCY
0.0 - MAXIMUM FREQUENCY
0.0 Hz
24
MAXIMUM FREQUENCY
MINIMUM FREQ - 240 Hz
60.0 Hz
25
CURRENT LIMIT
30 - 180 %
180 %
26
MOTOR OVERLOAD
30 - 100 %
100 %
27
BASE FREQUENCY
25.0 - 500.0 Hz
60.0 Hz
28
FIXED BOOST
0.0 - 30.0%
1.0%
29
ACCEL BOOST
0.0 - 20.0%
0.0%
PARAMETER MENU (cont)
27