beautypg.com

LEESON SM Series Sub-Micro Inverters User Manual

Page 31

background image

FACTORY

NO.

PARAMETER NAME

RANGE OF ADJUSTMENT

DEFAULT

12

TB-13E FUNCTION

NONE (01), 0-10 VDC (02), 4-20mA (03),

NONE (01)

SELECT

PRESET SPEED #3 (04), INCREASE FREQ (05),

START FORWARD (06), EXTERNAL FAULT (07),

INVERSE EXT FAULT (08), AUXILIARY STOP (09),

ACCEL/DECEL #2 (10).

TB-13E OUTPUT

RUN (11), FAULT (12), INVERSE FAULT (13),

SELECTIONS

FAULT LOCKOUT (14), AT SET SPEED (15),

ABOVE PRESET #3 (16), CURRENT LIMIT (17),

AUTO SPEED (18), REVERSE (19),

DYNAMIC BRAKING (20),

OTHER SELECTIONS

REMOTE KEYPAD (21)

14

CONTROL

TERMINAL STRIP ONLY (01),

TERMINAL STRIP

REMOTE KEYPAD ONLY (02),

ONLY (01)

16

UNITS EDITING

TENTHS OF UNITS (01),

WHOLE

WHOLE UNITS (02)

UNITS (02)

17

ROTATION

FORWARD ONLY (01),

FORWARD

FORWARD AND REVERSE (02)

ONLY (01)

19

ACCELERATION TIME

0.1 - 3600.0 SEC

20.0 SEC

20

DECELERATION TIME

0.1 - 3600.0 SEC

20.0 SEC

21

DC BRAKE TIME

0.0 - 3600.0 SEC

0.0 SEC

22

DC BRAKE VOLTAGE

0.0 - 30.0 %

0.0 %

23

MINIMUM FREQUENCY

0.0 - MAXIMUM FREQUENCY

0.0 Hz

24

MAXIMUM FREQUENCY

MINIMUM FREQ - 240 Hz

60.0 Hz

25

CURRENT LIMIT

30 - 180 %

180 %

26

MOTOR OVERLOAD

30 - 100 %

100 %

27

BASE FREQUENCY

25.0 - 500.0 Hz

60.0 Hz

28

FIXED BOOST

0.0 - 30.0%

1.0%

29

ACCEL BOOST

0.0 - 20.0%

0.0%

PARAMETER MENU (cont)

27