beautypg.com

KB Electronics KBPC-240D User Manual

Page 18

background image

15

2. Do not leave the motor in a locked condition for more than a few seconds since

armature damage may occur.

F. IR Compensation (IR) – The IR comp circuit is used to stabilize motor speed under

varying loads. (Note: If control is in Tach Feedback mode, the IR trimpot should be

set to minimum - ccw.) Readjust the IR trimpot as follows:
1. Run the motor at approximately 30-50% of rated speed under no load and measure

actual speed;

2. Load the motor to rated current. Rotate IR trimpot so that the loaded speed is the

same as the unloaded speed measured in 1.

Control is now compensated so that minimal speed change will occur over a wide range

of motor load. (Note: Too much IR Comp will cause unstable [oscillatory] operation.)

G. Timed Current Limit (TCL) – Jumper J5 must be in the "TCL" position, in order for Timed

Current Limit to be operational. This trimpot determines the approximate amount of time

the drive will stay in Current Limit before trip out. The trimpot has an adjustment range

of .5-15 seconds and is factory set for seven (7) seconds. The trimpot can be reset

according to the desired trip time. Rotating the trimpot clockwise increases the trip time.

This function provides motor overload protection. (See page 9, section II, E 1,

"Application Note," for TCL operation.)

H. Jog Speed (JOG) – This trimpot is operational only when the optional RUN-STOP-JOG

Switch is installed (KB P/N 9340). In the JOG position the JOG trimpot can be used to

set the JOG speed.

VIII. FUNCTION INDICATOR LAMPS.

The control contains three function LED Indicator Lamps that reflect its operational status.

A. Power On Indicator (ON) – This lamp will glow GREEN when the AC line is connected

to the control.

B. Stop Indicator (STOP) – This lamp will glow YELLOW when the control is placed in the

STOP mode with the Start/Stop Switch.

C. Overload Indicator (CL) – When the motor is loaded to the current limit setpoint (CL

setpoint is established by the setting of jumper J4 and the CL trimpot), this lamp will glow

RED. If the control is allowed to stay in CL and then trips out in Timed Current Limit, the

OL LED will remain lighted, until the control is restarted with the Start/Stop Switch. If the

OL LED remains lighted during control operation, a fault condition may exist. Possible

causes for this condition are as follows:
1. Motor is overloaded – Check motor amps with DC ammeter in series with armature.

(If motor is shunt type, field may be open or not receiving proper voltage.)

2. Motor may be defective – Check motor for shorts or grounds.
3. The CL may be set too low – Check position of jumper J4 and CL trimpot.
NOTE: In some applications, especially those requiring the motor to cycle on and

off or from one speed to another, the OL indicator may blink indicating a transient

overload. This may be a normal condition for the application.

IX. OPTIONAL ACCESSORIES.

A. RUN-STOP-JOG Switch (P/N 9340) – This switch provides a momentary jog speed that

can be used to "inch" a machine into position. It assembles easily to the control via quick

connect terminals. A rubber switch seal is included in order to maintain watertight

integrity.

B. Forward-Brake-Reverse Switch (P/N 9339) – This module provides a reversing function

along with dynamic braking. A special hesitation switch is used along with an Inhibit

function which minimizes arcing and plug-reversing. The installation is made simple with

the use of quick-connect terminals. Note: Signal Isolator (P/N 9431) cannot be

installed with Foward-Brake-Reverse Switch.

This manual is related to the following products: