beautypg.com

Securitron AQD3B User Manual

Page 7

background image

Page 7

P/N 500-30000

Rev. A, 04/13

Configure Status Monitoring
1. Wiring for AC Status Monitoring

The diagram below shows a basic wiring diagram to provide output to a
control panel or local alarm for notification of AC power loss.


AC-ON state energized the NO/C switch. The Switch changes state
when power is lost.

2.

Wiring for Limited Time Warning/Low Battery



The diagram shows wiring to an access system
controller to provide low battery warning.

It is also possible to provide a local indicator by
using an LED, 4.3K Ohm Resistor and 22-30 AWG
wire.

Testing
1.

Test Input and Outputs

AC Input: Enable AC power to input line. Confirm LED on front of enclosure is lit.

DC output: If connected to load or distribution board, DC output indicator on power module will be lit.

If not connected to load or distribution board, test output with Amp Meter to verify continuous current.

AC Fail Notification: Disable AC power to input line. If AC fail notification is configured, the switch will
change state, triggering the notification output.

LTW Notification: Disable AC power to input and allow batteries to run down to Limited Time Warning.

Recommended Annual Maintenance

AC Fail Notification Remove battery leads

Turn off AC power
Check AC fail notification
Restore Power
Remove battery leads
Turn off AC power
Check AC fail notification
Restore Power
Re-connect battery leads

Battery Test

Disconnect Power
Check DC output voltage under battery operation.
For fully charged batteries, voltage should be above 11.5VDC for 12 VDC setting and above 23.0 VDC for
24VDC operation. If voltage is below this range, test batteries per battery manufacturer instructions and
replace if needed.

Problems with installation? Call Securitron: 1-800-MAG-LOCK

For warranty information visit: www.securitron.com/en/site/securitron/About/MagnaCare-Warranty

LED

4.3K Ohm Resistor

+LTW

+LTW

Low Battery

Monitoring

Access Control
System Panel

NO C NC

AC Fail