Recommended Annual Maintenance
Battery Test
Turn off AC power
Check DC output voltage under battery operation.
For fully charged batteries, voltage should be above 11.5V. If voltage is below this range, test batteries
per battery manufacturer instructions and replace if needed.
AC Fail Test
Turn off AC power. AC Fail switch should trigger an alert upon disconnect or upon fail over to battery
power.