AQU244 & AQU128 Series Installation Instructions

AQU244 & AQU128 Series Instructions Doc.#500-33020 Rev. A

Page 4 of 5

Battery Selection

The table below shows typical standby time in hours for various loads and batteries. The table works for either
AQU244 24v, or AQU128 12v.
Approximate Battery Standby Time Table with a reserve of 3 Amps for 5 minutes for Alarm

Total Output

Amps

4Ah Battery

Standby

7Ah Battery

Standby

12Ah Battery

Standby

24Ah

Standby

40Ah

Standby

.5A

6.5 Hrs

13.2 Hrs

23.5 Hrs

47.5 Hrs

79.5 Hrs

1A

3 Hrs

6.3 Hrs

11.7 Hrs

23.7 Hrs

39.7 Hrs

2A

1.3 Hrs

2.5 Hrs

5.5 Hrs

11.2 Hrs

19.7 Hrs

3A

.7 Hrs

1.5 Hrs

3.6 Hrs

7.2 Hrs

13 Hrs

4A

.5 Hrs

1 Hrs

2.3 Hrs

5 Hrs

9.6 Hrs

5A

NA

.8 Hrs

1.7 Hrs

3.7 Hrs

7.4 Hrs

6A

NA

.6 Hrs

1.3 Hrs

3. Hrs

5.5 Hrs

7A NA NA

1.1

Hrs 2.2

Hrs 4.4

Hrs

8A

NA

NA

.8 Hrs

1.8 Hrs

3.4 Hrs

The recharge table below gives approximate recharge times for different loads and battery sizes. The table is
based on batteries depleted to battery cut-off and recharged back to approximately 90% capacity.

Approximate Battery Recharge Times in Hours

Total Output

Amps

4Ah Battery

12/24

7Ah Battery

12/24

12Ah Bat

12/24

24Ah Bat

12/24

40Ah Bat

12/24

.5A

8/8 10/10 11/11 12/12 14/14

1A

8/8 10/10 11/11 12/12 14/14

2A

8/8 10/10 11/11 12/12 14/14

3A

8/8 10/10 11/12 12/14 14/16

4A 8/10 10/12 11/14 12/16 14/20

5A 8/NA

10/NA

11/NA 12/NA 14/NA

6A 8/NA

11/NA

12/NA 14/NA 15/NA

7A 8/NA

12/NA

13/NA 15/NA 17/NA

8A 12/NA 14/NA 16/NA 18/NA 20/NA

Maintenance

The power supply and stand by battery(s) should be tested at least once a year as follows:

1. Check LED’s for normal state. AC ON Green, Trouble ON Green, DC ON Red.
2. Check output voltage with normal load. The AQU128 should read between 13.60 and 13.85vdc. The

AQU244 should read between 27.00 and 27.8vdc. This assures proper voltage to float charge batteries.

3. Disconnect AC input. AC LED should be off, all other LED’s should remain normal.
4. Check DC Output to be above 12.1vdc for AQU128 and 24.2vdc for AQU244. This checks standby

batteries to be operational. Sealed lead acid batteries have a typical life of 3 to 5 years.

5. Re Apply AC and verify AC LED ON.

Lead acid batteries have a typical life of 3 to 5 years.