Operating guidelines, Using the selection menu, A. tank fill (r-12 users) – Robinair 348012K Recovery, Recycling, Recharging Unit User Manual
Page 9
7
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
USING THE SELECTION MENU
(continued)
4-a. TANK FILL (R-12 Users)
NOTE: If using a refillable tank, place the tank upside down and connect the
lowside service hose to the vapor valve.
Set SELECTOR switch to R-12:
1. Connect the 6" yellow adapter to the end of the low side service hose.
2. Connect the low side service hose to the source tank and open valve.
3. Select TANK FILL from the Selection Menu.
4. Press
ENTER
. Then press
START
and the tank automatically refills. The
unit stops when a sufficient amount of refrigerant has been transferred to the
ESV- or - the source tank is empty.
NOTE: Press
STOP
if you wish to stop fill before it completes.
5. Close the valve on the source tank.
6. Disconnect the 96" blue service hose from the adapter, then disconnect the
6" yellow adapter from the source tank.
7. Press
STOP
to exit.
Operating Guidelines
ESV
INST0710
Source
Tank
R-12
Low Side
Service Hose