beautypg.com

Maintenance, Archive, Routine preventive – Ransburg 9040 Classic HV Power Supply 77070-33 User Manual

Page 20: Troubleshooting

background image

CP-08-01

MAINTENANCE

MAINTENANCE

MAINTENANCE

MAINTENANCE

MAINTENANCE

ROUTINE PREVENTIVE

ROUTINE PREVENTIVE

ROUTINE PREVENTIVE

ROUTINE PREVENTIVE

ROUTINE PREVENTIVE

MAINTENANCE

MAINTENANCE

MAINTENANCE

MAINTENANCE

MAINTENANCE

In general, little maintenance is necessary to
ensure proper operation. However, it is important
to keep the interior of the unit clean and free from
moisture or foreign material. For this reason the
following must be done:

1. Keep the exterior of the unit free from dust
accumulation.

2. Always clean the exterior prior to opening the
cabinet door.

3. Open the cabinet door only to perform
maintenance or repair.

4. If the power supply end of the high voltage
cable becomes dirty, clean the end of the cable
with a suitable, clean, non-polar solvent and apply
a light coat of dielectric grease. On a yearly basis,
check to ensure that the LSCH-0009 dielectric
lubricant is covering the electrical contact point in
the high voltage tube. If not, add oil as needed.

TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

PC Board T

PC Board T

PC Board T

PC Board T

PC Board Test Jumper

est Jumper

est Jumper

est Jumper

est Jumper

To assist in testing and troubleshooting, a jumper
(JP4) has been incorporated on the 9040 PC
board. By covering (shorting) both terminals, the
high voltage on relay is triggered. Thus, for testing
and troubleshooting, high voltage output can be
obtained without the need to trigger the spray
applicator or user supplied control device. Just
remember to reposition the jumper after testing, so
that it covers only one terminal or the high voltage
will stay on all the time. (See Figure 5 for location
of test jumper JP4.)

Figure 5: Main PC Board

Figure 5: Main PC Board

Figure 5: Main PC Board

Figure 5: Main PC Board

Figure 5: Main PC Board

>

Applying LSCH-0009 dielectric lubri-

cant to the high voltage cable end signifi-
cantly reduces corona discharge that can
cause deterioration of the high voltage
connection components.

N O T E

N O T E

N O T E

N O T E

N O T E

>

If JP4 is left covering (shorting) both

terminals, high voltage will be on whenever
AC power is turned on. This could be
hazardous in some applications.

C A U T I O N

C A U T I O N

C A U T I O N

C A U T I O N

C A U T I O N

!!!!!

9040 Classic HV Power Supply - Maintenance

1 7

1 7

1 7

1 7

1 7

ARCHIVE