Remote mode only operations, 9060 high voltage controller - operation, Adjusting presets – Ransburg 9060 HV Auto Classic 80100-XXX User Manual
Page 42: Tripleset selection, Resetting faults
9060 High Voltage Controller - Operation
37
CP-13-05.2
Adjusting Presets
To adjust one of the preset setpoints, ensure
the applicator is off in LOCAL mode and select
the desired setpoint by pressing the corre-
sponding setpoint button. The setpoint can then
be adjusted between 20 kV and full kV using
the + and - buttons on the front panel of the
9060 Controller shown in Figure 31. Single
pushes of the + or - buttons will increment or
decrement the currently selected preset in units
of 1. When the + or - buttons are held in for
longer than 1 second, the kV display will begin
incrementing or decrementing in units of 5.
The three setpoints can ONLY be ad-
justed in LOCAL mode.
N O T E
REMOTE MODE ONLY
OPERATIONS
Tripleset Selection
The tripleset signals are used to select voltage
setpoints (presets) that are used during Local
Mode operation. To select a setpoint, the
tripleset signals must be set to the correspond-
ing binary combination as listed in the Tripleset
Selection Table.
TRIPLESET SIGNAL TIMING:
The minimum hold time for the setpoint selec-
tion signals is 10 ms.
Resetting Faults
During operation, various faults can occur
based upon the operating conditions or if any
problems with the 9060 unit arise. If a fault
occurs, to reset a fault, the trigger signal MUST
be off and then press the Reset Button. This
will clear the fault status and put the unit back
into operation unless a fault condition is still
present. Please refer to the “Fault Description”
portion of the Operation Section of this Service
manual for more information on a specific fault
and how to correct it.
TS1
TS0
Selection
0 (off)
0 (off)
No Change
0 (off)
1 (on)
Preset 1
1 (on)
0 (off)
Preset 2
Tripleset Selection
1 (on)
1 (on)
Preset 3
After the hold time, the simultaneous
signals can be returned to off, but they
must be at the same time to avoid falsely
selecting a different setpoint.
N O T E
The presets can NOT be adjusted in
remote mode. The unit must be in LO-
CAL mode and the preset values must be
adjusted using the front panel.
If adjustable voltage setpoints are
needed, analog kV setpoint signaling is
required.
N O T E
For tripleset to control the kV setpoint,
no analog kV set signal should be active.
!
C A U T I O N
Figure 31: kV Adjust/Setpoint Buttons
There is a 5 second fault reset delay
timer that inhibits the triggering of high
voltage immediately after a fault reset.
N O T E