FIREPOWER XLSV User Manual
Page 4

at 25VRMS, 180 watts of audio at 70VRMS or 165 watts of
audio at 100 VRMS. It mounts in one module space on the
CAB-MP mounting plate. The ZAM-180 is capable of
amplifying any one of the 8 digital audio channels that are
transmitted from the DAC-NET (Digital Audio Card) via the
digital audio bus ASI (Audio Serial Interface). The ZAM-180
amplifier is supervised for functionality.
The ZAM-180 can be used as a single 180 Watt speaker
zone for one to eight channel applications or as a bulk
amplifier for one or two channel applications feeding high
level audio to the ZIC-4A or ZIC-8B.
FMT Fireman's Master Telephone
The FMT provides firefighters with an emergency tele-
phone system for communication with remote locations.
The FMT mounts to the rear of the Inner Door of a CAB1,
CAB2, CAB3, or REMBOX4 Enclosure. It includes a
handset for the operator of the telephone system.
The XLSV firefighter's telephone unit is designed for
maximum performance in communication. The FMT
circuitry allows the master telephone and at least 5
telephone stations to be off hook simultaneously with no
degradation of audio quality.
The FMT also supports Warden Page function which allows
live voice announcements from any remote telephone.
Telephone zone call-ins are annunciated on the appropriate
SCM-8 switch module. Remote stations receive an
acknowledge tone when dialing into the command center
prior to the call being answered indicating a call-in in
progress and a busy tone if calling into the command
center and another telephone zone is already on line.
Diagnostic LEDs are located on the back of the FMT to
indicate power is applied to the module and failure of the
card, CAN communication or phone.
FMT
TZC-8B Firefighter's Telephone Zone Card
The TZC-8B provides a way for emergency response
personnel located throughout a building to speak to one
another during emergency situations.
The TZC-8B is an XLSV option module which plugs into a
CC-2 or CC-5 card cage providing 8 firefighters telephone
zones. The zones have an off-hook acknowledge tone as
well as a Command Console busy tone.
Each telephone zone uses a single pair of wires and is
individually supervised in a Class B type mode. Field
wires are connected to one or more phone jacks or sta-
tions.
Zones are also individually power limited per NEC 760.
Each zone also contains transient protection.
Up to 5 telephone stations may be off-hook simulta-
neously in a party line mode with no loss of audio quality.
HCP
The HCP provides an intelligent control point for the
FireFinder XLS Control Panel. The HCP can be
programmed as an independent, remotely located tele-
phone zone, speaker zone or notification appliance circuit.
The HCP is designed to be used with the Siemens Fire
Safety notification appliance product line. The HCP commu-
nicates through the DLC analog loop and can be wired
either Class A (Style Z) or Class B (Style Y).The 24 VDC
power input comes from either the control panel or from
any UL listed power limited, auxiliary power supply.
TZC-8B
HCP