FIREPOWER XLSV User Manual
Page 2

Remote paging can be provided from any telephone zone
(Warden's Page) with selection at the command console.
In addition, specific telephone zones can be pre-selected
as automatic page zones on a selective or All Call basis.
Speaker zones are selectable for either 25 Volt or 70.7 Volt
operation and either Style Y (Class B) or Style Z (Class A)
wiring configuration. Strobe circuits may also be wired as
Style Y or Style Z.
Speaker, Strobe and Firefighter's Telephone zones can be
provided as either modules or plug-in type cards, installed
in the main enclosure or remote voice system transpon-
ders. The cards are plugged into the standard XLS CC-5/
CC-2 card cages. The XLS Control Point Module HCP can
also be used to provide a remote telephone zone, speaker
zone or notification appliance circuit.
SCM-8 Switch Control Module
The SCM-8 is a FireFinder XLS option module which
provides manual control of the Emergency Voice Evacua-
tion System or manual fire system control. Each SCM-8
module provides eight momentary pushbutton switches
and 16 LED's to indicate their status. Each switch is
assigned two LED's and a label to indicate the switch's
programmed usage. The label slides behind a clear
protective membrane. One of the LED's assigned to each
switch is a dual color LED used to indicate what type of
signal is active.
Each SCM-8 and each switch is fully programmable and
may be used to control speaker circuits, and a wide range
of general system functions such as All Call, All Evac,
Warden's Page, Speaker, etc. Any number of circuits may
be grouped and controlled by a single switch. Switch
usage and zone groupings are assigned using the ZEUS
system programming software.The SCM-8s are mounted
on a hinged panel as a partof the FireFinder XLS Command
Console enclosure.
SCM-8
LCM-8
FCM-6
LCM-8 LED Control Module
The LCM-8 is an FireFinder XLS option module which
provides LED annunciation of system activity. Each LCM-
8 module contains eight groups of 2 LED's, each of which
can be assigned to desired outputs using the ZEUS
programming software. Eight LED's are dual color capable
of being lighted either RED or GREEN flashing or steady.
The remaining LED's are AMBER flashing or steady. A
space is provided for labeling of LED functions. The label
slides behind a clear protective membrane. The LCM-8
dimensions are identical to the SCM-8 and is mounted on
the same hinged panel as a part of the FireFinder XLS
Command Console enclosure.
FCM-6 Fan, Motor, dampers Control Module
The FCM-6 is an FireFinder XLS command console option
module that provides manual control of building HVAC
system fans, motors, and dampers. EachFCM-6 module
provides (6) sets of (3) push button switches for manual
system control. Each switch has 3 associated LEDs to
indicate Fan/Damper/Motor status: OFF (Red LED), ON
(Green LED), TROUBLE(Yellow LED).