beautypg.com

Teledyne 7320 - NDIR analyzer User Manual

Page 22

background image

2 Installation

Model 7320

2-8

Teledyne Analytical Instruments

2.3.3.3

Digital Remote Cal Inputs

Accept 0 V (off) or 24 V dc (on) inputs for remote control of calibra-

tion. (See Remote Calibration Protocol below.) See Figure 2-5 for pin
connections.

Zero:

Floating input. A 5 to 24 V pulse input across the + and –
pins puts the analyzer into the

Zero

mode. Either side may be

grounded at the source of the signal. A synchronous signal
must open and close the gas control valves appropriately.

Span:

Floating input. A 5 to 24 V pulse input across the + and –

pins puts the analyzer into the

Span

mode. Either side may

be grounded at the source of the signal. A synchronous signal
must open and close the gas control valves appropriately.

Cal Contact: This relay contact is closed while analyzer is spanning

and/or zeroing. (See Remote Calibration Protocol below.)

Table 2-5: Remote Calibration Connections

Remote Calibration Protocol: To properly time the Digital Remote

Cal Inputs to the Model 7320 Analyzer, the customer's controller must
monitor the Cal Relay Contact.

When the contact is OPEN, the analyzer is analyzing, the Remote Cal

Inputs are being polled, and a zero or span command can be sent.

When the contact is CLOSED, the analyzer is already calibrating. It

will ignore your request to calibrate, and it will not remember that request.

R E M O TE
SPAN (2 4V )

R E M O TE
ZE R O (24V )

+

+

P re s s h e re to
in se rt w ire .
R e le a se to h o ld .

In s e rt w ire
h e re .

DIGITAL INP UTS

F lo a tin g