beautypg.com

Teledyne 3000PA - General purpose percent oxygen analyzer User Manual

Page 45

background image

Percent Oxygen Analyzer

Operation 4

4-13

Teledyne Analytical Instruments

“C" contacts rated for 3 amperes resistive load at 250 V ac. See Figure in
Chapter 3, Installation and/or the Interconnection Diagram included at the
back of this manual for relay terminal connections.

The system failure alarm has a fixed configuration described in chapter

3 Installation.

The concentration alarms can be configured from the front panel as

either high or low alarms by the operator. The alarm modes can be set as
latching or non-latching, and either failsafe or non-failsafe, or, they can be
defeated altogether. The setpoints for the alarms are also established using
this function.

Decide how your alarms should be configured. The choice will depend

upon your process. Consider the following four points:

1. Which if any of the alarms are to be high alarms and which if any

are to be low alarms?

Setting an alarm as HIGH triggers the alarm when the oxygen
concentration rises above the setpoint. Setting an alarm as LOW
triggers the alarm when the oxygen concentration falls below the
setpoint.

Decide whether you want the alarms to be set as:

Both high (high and high-high) alarms, or

One high and one low alarm, or

Both low (low and low-low) alarms.

2. Are either or both of the alarms to be configured as failsafe?

In failsafe mode, the alarm relay de-energizes in an alarm
condition. For non-failsafe operation, the relay is energized in an
alarm condition. You can set either or both of the concentration
alarms to operate in failsafe or non-failsafe mode.

3. Are either of the alarms to be latching?

In latching mode, once the alarm or alarms trigger, they will
remain in the alarm mode even if process conditions revert back
to non-alarm conditions. This mode requires an alarm to be
recognized before it can be reset. In the non-latching mode, the
alarm status will terminate when process conditions revert to non-
alarm conditions.

4. Are either of the alarms to be defeated?

The defeat alarm mode is incorporated into the alarm circuit so
that maintenance can be performed under conditions which
would normally activate the alarms.