beautypg.com

Control unit - block diagram – Teledyne 1220 - Multipoint flammable gas and vapor detection system User Manual

Page 12

background image

2-2

2 Operational Theory

Model 1220

Teledyne Analytical Instruments

for operation in the “non fail-safe” mode by setting the configuration
jumpers as indicated in the installation section 3.3.2. Each of these relays
provides SPDT contacts for operation of external devices.

An audible alarm is actuated when any alarm state occurs. This

audible alarm may be disconnected by switching the AUDIBLE ALARM
control switch to the BYPASSED position. When this is done, the red
lamp on the system module is illuminated as an indication that the audible
alarm is not functioning.

The Control Unit is the power entry and distribution point. The 1220

system contains universal power supplies that operate on 100-240 VAC,
50/60Hz. The power switch on the Control Unit switches power for the
entire system. The line is protected by two 3 Amp fuses, accessible from
the front panel.

A 1/8 A fuse is furnished for the electronic circuitry of the Control

Unit. The green power LED indicates that the Unit is ON.

Alarm switch S2 has two positions. Normally, the switch is set to the

ACTIVE position which provides for audible alarm when any of the
Channel Modules goes into the alarm state. When set to the BYPASS
position, the local audible alarm is turned off.

SIGNALS FROM
CHANNEL MODULES

POWER

SWITCH

INTERNAL
BUZZER

PRIMARY
POWER

DRIVERS

RELAYS

AUDIBLE

ALARM BYPASS

*HIGH

*CAUTION

FAILURE

POWER TO

CHANNEL

MODULES

POWER FOR
EXTERNAL
AUDIBLE
ALARMS

CAUTION

FAILURE

RELAY
CONTACT
ACTUATION

HIGH

Control Unit - Block Diagram