Operators Instructions for

Transformer Oil Pumps

Manual No/Rev

W61-001E / 9

Our policy is one of continuous improvement and we reserve the right to alter specifications without giving notice.

Page 9

1


4.6.1 Three-phase Supply Units

Check phasing of supply is to the
standard phase sequence of Red-
Yellow-Blue. Connect wiring as
shown in the diagram.

It is essential to check that the

wiring gives the correct direction
of pump rotation. For this
purpose only, the pump may be
run very briefly without oil
lubrication/cooling.


To check rotation before suction pipework is connected:

Visually check through the suction branch that the rotation is as shown on
the casing.


To check rotation with pump installed

A "Phase & Continuity Indicator", connected to the correct pump terminals,
will give confirmation of the direction of rotation.


The visual indicator, fitted to some pumps, will also show the direction of
rotation when filled with oil.


Note: Do not rely on the direction of oil flow. Some types of pump will give

the same direction of flow whatever the rotation.



4.6.2 Single Phase

TERMINAL

MAINS SUPPLY

CABLE

Connect electrical power supply

Z1/U1

Brown

cables as shown in the table

V1/U2

Black

See also the label inside the

W1/Z2

One capacitor lead

terminal box cover.

V1/U2

Other capacitor lead

W1

U1

Z1

Z2

U2

V1

TERMINAL

U1/Z1

BROWN

TERMINAL

W1/Z2

GREY

TERMINAL

V1/U2

BLACK

ATTENTION