27. *Slave 8 stage order [LLSlv8Ordr] 0799

a. Relative order that slave 8 has been added to fire

b. 0=Not been staged

28. *Slave 8 firing rate [LLSlv1FR] 0800

a. Current firing rate (0-100%) of slave 8

29. *Active lead lag setpoint [LLSetpntF] 0018

a. -40˚C - 130˚C (will display as -40˚F - 266˚F)

30. *Active lead lag operating point [LLOprtingF] 0027

a. -40˚C - 130˚C (will display as -40˚F - 266˚F)

31. Inlet Sensor State [InletState] 0049

a. 0=none

b. 1=Normal

c. 2=open

d. 3=shorted

e. 4=outside high range

f. 5=outside low range

g. 6=not reliable

32. Inlet (S1) sensor [InletTempF] 0011

a. -40˚C - 130˚C (will display as -40˚F - 266˚F)