Fulton Caliber (CAL) SOLA Gateways User Manual
Page 29
![background image](/manuals/345488/29/background.png)
__________________________________________________________
_____________________________________________________________________________________
Questions? Call (315) 298-5121 or visit us online at
www.fulton.com
©The Fulton Companies 2013
Supplement SOLA-IOM-2013-0220
27. *Slave 8 stage order [LLSlv8Ordr] 0799
a. Relative order that slave 8 has been added to fire
b. 0=Not been staged
28. *Slave 8 firing rate [LLSlv1FR] 0800
a. Current firing rate (0-100%) of slave 8
29. *Active lead lag setpoint [LLSetpntF] 0018
a. -40˚C - 130˚C (will display as -40˚F - 266˚F)
30. *Active lead lag operating point [LLOprtingF] 0027
a. -40˚C - 130˚C (will display as -40˚F - 266˚F)
31. Inlet Sensor State [InletState] 0049
a. 0=none
b. 1=Normal
c. 2=open
d. 3=shorted
e. 4=outside high range
f. 5=outside low range
g. 6=not reliable
32. Inlet (S1) sensor [InletTempF] 0011
a. -40˚C - 130˚C (will display as -40˚F - 266˚F)