Maintenance, Troubleshooting – Fulton Electric (FB-L) Steam Boiler User Manual
Page 32

Troubleshooting
Problem
Cause
Check
Primary Voltage Circuit
C. Wiring Connections
With power off, check continuity of circuit through each
point in the circuit. If a break in the circuit is found,
repair. After repair, recheck with continuity light with
power off. Turn power on and check with an amp meter.
D. Burned or Broken Wiring
With power off, check continuity of circuit through each
point in the circuit. If a break in the circuit is found,
repair. After repair, recheck with continuity light with
power off. Turn power on and check with an amp meter.
Verify wire size is sufficient for amp draw.
E. Contactor Contact Points
If burned or dirty, clean with fine emory paper. If burned
through, replace. If not engaging completely,coil may be
weak. Replace.
F. Elements Shorting or Open Circuit
With power using a continuity tester, check to see if an
element is burned out between each point. If power is
on, a volt meter may be used. If an element is bad,
replace.
Low Water Condition
A. Circulating Pump
Clean or replace all filters or screens to assure proper
water flow through them.
B. Water Makeup Supply
Check to see that your supply water has not been shut
off or that there are no restrictions in the line leading to
the boiler.
C. Leaks in the System
Check piping for any leaks.
Scale Formation Elements
A. Hardness, Salt, Precipitation
Softener perfomance
B. High Dissolved Solids
Blowdown Schedule
Poor Steam Quality
A. High Alkalinity in Boiler Water
Adequate blowdown schedule or over feeding of water
B. High Organics in Boiler Water
treatment chemicals
C. High Total Dissolved Solids in Boiler Water
28
Maintenance
Electric IOM