PSA LIF5800RL User Manual
Page 8
6
6
6.1.3 This Smoke Alarm can only interconnect with LIFESAVER Model 5000,
5800, 5800RL, 3000, 4800RL Smoke Alarms; Heat Alarm model HA240 and
visual Signaling Device model SL240 and isolation relay model RK10A/9.
Interconnection with other brands may cause damage or result in a shock or
fire risk and void warranty.
6.1.4 Due to “noise” from electromagnetic interference, up to 24 units of smoke
alarms and compatible products may be interconnected.
6.1.5 There are five terminals in the supply terminal block, marked 9V, A, SW, N,
LOOP. It is important that the alarm be wired correctly to ensure correct opera-
tion. Incorrect wiring to the Smoke Alarm will damage the unit and void the
warranty.
6.1.6 A total maximum of 250 meters (820 feet) of wire can be used in interconnect-
ing smoke alarms.
6.1.7 All final sub-circuit conductors including the signal conductor must be a mini-
mum size of 1mm² with 250V grade insulation.
6.1.8 Interconnected Smoke Alarms must be connected to the same final subcircuit.
6.1.9 Do not use any wire that could later be confused with the normal house wires
for the interconnect wire. For example, green/yellow earth wire.
6.1.10 Do not connect AC power wires to SW interconnect terminal. These will dam-
age smoke alarms.
6.1.11 Do not connect the SW interconnect wire to any device, except the SW inter-
connect terminal of smoke alarm. Otherwise, smoke alarm will be damage.
6.1.12 Switch wire (SW) only can drive the RK10A/9 and smoke alarms.
6.1.13 Do not connect 9V wire to AC power or SW interconnect terminal.These may
damage smoke alarms.
6. INSTALLATION
1398-7208-03:_ 2012.6.13 4:24 PM Page 6