Perma Pure Micro-GASS UG-1212 User Manual

Page 21

background image

Appendix C – CAL 3300 Temperature Controller Configuration


1 For all Micro-GASS systems with the CAL3300 Temperature controller, perform the following

setup procedures.

a Power Up - Apply power to the system and wait for the controller to perform its self test

routine. The display will then be alternately flashing “nonE” and “inPt”.

b Input sensor type - Press and hold º key. Press S key repeatedly to select the “tc K

option for K type thermocouple. Release both keys.

c Input unit type - Press the S key once. The display will then be alternately flashing “unit

and “nonE”. Press and hold the º key. Press S key repeatedly to select the “

O

C

” unit.

Release both keys.

d Input setpoint 1 type - Press the S key once. The display will then be alternately

flashing “SP1.d” and “nonE“. Press and hold the º key. Press S key once to select the
output device ”SSd”. Release both keys.

e Input the maximum temperature setpoint - Press and hold the T key until “LEVL

appears. Press and hold the º key. Press the T key to move to level 2. Release the two
keys. Press and hold the S key until “hi.SC” appears. Press and hold the º key. Press
the T key until “65” appears. Release the two keys.

f Input the minimum temperature setpoint Press the S key once. “Lo.SC” appears.

Press and hold the º key. Press the S key until “45” appears. Release the two keys.

2 Configure the low temperature alarm.

a Configure SP2 relay as alarm - Press and hold S and T keys simultaneously for 3

seconds to enter the program mode. Release the two keys. The display will then be
alternately flashing “tunE” and “oFF”. Press the T key once. The display will then be
alternately flashing “LEVL” and “1”. Press and hold the

º

key. Press the S key once to

move to level 2. Release the two keys. Press and hold the S key until “SP2.A” appears.
Press and hold the º key. Press the S key until the display reads FS.Lo. Release the two
keys. The display will then be alternately flashing “SP2.A” and “FS.Lo”.

b Save configuration into memory - Press and hold S and T keys simultaneously for 3

seconds. The display will then be alternately flashing the process temperature and “PArK
indicating that no setpoint temperature has been entered.

3 Set the control setpoint and auto-tune the controller.

a Input the control setpoint temperature - Press and hold the º key. Hold the S key until

the display goes from 0 to 65.

b Auto-tune the controller - Press and hold S and T keys simultaneously for 3 seconds to

enter the program mode. Release the two keys. The display will then be alternately
flashing “tunE” and “oFF. Press and hold the º key. Press the S key until “At.SP
appears. Release the two keys. Press and hold S and T keys simultaneously for 3

21