12.5 Programming Points 1 and 2 (SPH)
If you wish to program the response in strokes per hour, start by
being in the External mA mode. Next, switch to the Internal mode.
If the Internal setting is in strokes per minute, change to strokes per
hour by holding the
(Down) key until the display reads 0 SPM.
Continue to hold it for another three (3) seconds. The display will
now read SPH
INT
. Set the speed to any SPH value (the actual
setting has no bearing on mA response). Return to the External mA
mode.
In the External mA mode, pressing the
(Down) key or
(Up)
key will change the display to
. After five (5) seconds, the
display will show the mA value for P1
P1
mA
. This value may be
altered by using the
(Up) key or
(Down) key within five
(5) seconds (i.e.
). Five (5) seconds following the last key
press, the stroke rate for P1 will be displayed
. This value
may be altered within five (5) seconds using the
(Up) or
(Down) key (i.e.
).
Five (5) seconds after the last key press, the mA value for P2 will
be displayed
P2
mA
. Edit as described above (i.e.
P2
mA
).
Likewise, five (5) seconds after the last keypress, the stroke rate for
P2 is displayed and may be altered as above (i.e.
P2
).
The above example would result in the inverse control profile shown
in Figure 14 on the following page.